THE EFFECT OF AC SYSTEM FREQUENCY-SPECTRUM ON COMMUTATION FAILURE IN HVDC INVERTERS

被引:45
作者
KRISTMUNDSSON, GM
CARROLL, DP
机构
[1] Department of Electrical Engineering, University of Florida, Gainesville
关键词
D O I
10.1109/61.53130
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Previous studies have shown that many types of system disturbances will lead to commutation failure at HVdc inverter stations. The problem is further aggravated if the inverter is connected to a weak (low SCR) ac system. This paper analyzes the problem in terms of the frequency spectrum of the ac network and its relation to the transient disturbance which causes the failure. Methods are discussed for modifying the frequency spectrum in order to decrease the probability of commutation failure. A sample simulation study was performed to illustrate the effectiveness of one particular type of filter. Results indicate that in some cases the probability of failure can be reduced dramatically. © 1990 IEEE