Time-domain application of superimposed quantities in the phase comparison transmission line protection scheme

被引:5
|
作者
Silva Leite Junior, Eduardo Jorge [1 ]
Lopes, Felipe Vigolvino [1 ]
Silva, Kleber Melo [1 ]
机构
[1] Univ Brasilia, Dept Elect Engn, Brasilia, DF, Brazil
来源
关键词
power transmission lines; power transmission faults; power system relaying; fault diagnosis; power transmission protection; relay protection; time-domain analysis; sequence currents; traditional incremental currents; incremental replica currents; PC protection reliability; protection operation times; time-domain application; superimposed quantities; phase comparison transmission line protection scheme; time-domain phase comparison; modern high-speed protection relays; protection functions; alternative transients programme; fault scenarios; different fault features; system loading conditions; tripping times; traditional phase currents; time-domain PC line protection schemes; voltage; 500; 0; kV; frequency; 60; Hz;
D O I
10.1049/joe.2018.0277
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Here, the use of incremental currents in time-domain phase comparison (PC) line protection schemes is evaluated. The incremental currents have been applied in modern high-speed protection relays, showing to be suitable for protection functions based on time-domain analysis. To carry out the proposed studies, the alternative transients programme was used to simulate a wide variety of fault scenarios in a 500kV/60Hz test power system, considering different fault features (distance, resistance, and inception angle), source-to-line impedance ratio values, and system loading conditions. In each case, the tripping times of the time-domain PC protection when implemented using traditional phase currents, sequence currents, traditional incremental currents, and incremental replica currents are compared. The obtained results show the use of incremental currents improves the PC protection reliability, speeding up the protection operation times.
引用
收藏
页码:1360 / 1364
页数:5
相关论文
共 50 条
  • [1] Transient Protection Scheme of HVDC Transmission Line Based on Time-domain Voltage Ratio
    Chen X.
    Li H.
    Gu G.
    Liang Y.
    Wang G.
    Li, Haifeng (lihf@scut.edu.cn), 1600, Automation of Electric Power Systems Press (44): : 62 - 69
  • [2] A Hybrid Time-Domain Protection Scheme for Series Compensated Transmission Lines
    Naidu, O. D.
    Pradhan, Ashok Kumar
    George, Neethu
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 1823 - 1833
  • [3] Transmission-Line Protection: A Directional Comparison Scheme Using the Average of Superimposed Components
    Hashemi, S. M.
    Hagh, M. Tarafdar
    Seyedi, H.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (02) : 955 - 964
  • [4] Guidelines for EMT Transmission Line Models for Time-Domain Protection Algorithms
    Vermunicht, Joachim
    Leterme, Willem
    Abedrabbo, Mudar
    Van Hertem, Dirk
    2023 IEEE BELGRADE POWERTECH, 2023,
  • [5] Subcycle transmission line protection using time-domain similarity measure
    Sirisha, A. N. R. L.
    Pradhan, Ashok Kumar
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 137
  • [6] Robust phase-domain transmission line representation based on time-domain fitting
    Nobre, DM
    Boaventura, WD
    Neves, WLA
    ELECTRIC POWER SYSTEMS RESEARCH, 2006, 76 (08) : 608 - 615
  • [7] On the time-domain transmission-line equations
    Faria, JAB
    MICROWAVE AND OPTICAL TECHNOLOGY LETTERS, 1999, 22 (03) : 194 - 197
  • [8] Sparse two-phase transmission line representation in phase-domain based on time-domain fitting
    Nobre, DM
    Boaventura, WC
    Neves, WLA
    2004 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION: LATIN AMERICA, 2004, : 675 - 680
  • [9] Modelling and simulation of a time-domain line protection relay
    Ribeiro, Joao Paulo G.
    Lopes, Felipe V.
    JOURNAL OF ENGINEERING-JOE, 2018, (15): : 861 - 865
  • [10] A current differential protection using time-domain waveform comparison for HVDC transmission lines
    School of Electrical Engineering, Xi'an Jiaotong University, Xi'an
    710049, China
    不详
    710054, China
    Dianli Xitong Zidonghue, 24 (87-95):