Comparative study of cycle modification strategies for trans-critical CO2 refrigeration cycle for warm climatic conditions

被引:20
作者
Singh, Simarpreet [1 ]
Purohit, Nilesh [1 ]
Dasgupta, M. S. [1 ]
机构
[1] BITS Pilani, Dept Mech Engn, Pilani, Rajasthan, India
关键词
Trans-critical CO2 refrigeration cycle; Exergy; FGB; FGI; IHX; Expander;
D O I
10.1016/j.csite.2016.03.002
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a comparative study of performance of six prominent modifications on the basic trans-critical CO2 refrigeration system to investigate their suitability to high ambient temperature application (35-55 degrees C). To explore the application in chiller, domestic refrigeration and air cooling the evaporator temperature chosen are -10 degrees C, 0 degrees C and 10 degrees C respectively. In general the cycle modifications have a positive effect on the overall COP of the system. However, to comprehend practicability of these modifications for three application areas, a few other parameters which affect design and operation are also included in the study. These are compressor discharge pressure and temperature, mass flow rate, interstage pressure for multi-stage operation and exergy destruction. Effect of real time constraints like approach temperature, pressure drop in gas cooler, compressors efficient', degree of superheat, expanders efficiency and effectivenesss of intermediate heat exchanger are also incorporated. Interrelation between these parameters are brought out from the study. (C) 2016 Published by Elsevier Ltd.
引用
收藏
页码:78 / 91
页数:14
相关论文
共 14 条
[1]   Optimization of two-stage transcritical carbon dioxide heat pump cycles [J].
Agrawal, Neeraj ;
Bhattacharyya, Souvik ;
Sarkar, J. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2007, 46 (02) :180-187
[2]   Simulation and performance optimization of finned tube gas cooler for trans-critical CO2 refrigeration system in Indian context [J].
Gupta, Dileep Kumar ;
Dasgupta, M. S. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 38 :153-167
[3]  
Hwang Y.H., 2004, INT REFR AIR COND C
[4]  
Kadam A.D., 2013, IJCER, V3, P3
[5]   The performance of a transcritical CO2 cycle with an internal heat exchanger for hot water heating [J].
Kim, SG ;
Kim, YJ ;
Lee, G ;
Kim, MS .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (07) :1064-1072
[6]   THE USE OF NATURAL REFRIGERANTS - A COMPLETE SOLUTION TO THE CFC/HCFC PREDICAMENT [J].
LORENTZEN, G .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (03) :190-197
[7]   Efficiencies of transcritical CO2 cycles with and without an expansion turbine [J].
Robinson, DM ;
Groll, EA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (07) :577-589
[8]   Energetic evaluation of a CO2 refrigeration plant working in supercritical and subcritical conditions [J].
Sanchez, Daniel ;
Patino, Jorge ;
Sanz-Kock, Carlos ;
Llopis, Rodrigo ;
Cabello, Ramon ;
Torrella, Enrique .
APPLIED THERMAL ENGINEERING, 2014, 66 (1-2) :227-238
[9]   Optimization of a transcritical CO2 heat pump cycle for simultaneous cooling and heating applications [J].
Sarkar, J ;
Bhattacharyya, S ;
Gopal, MR .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (08) :830-838
[10]   Energetic evaluation of an internal heat exchanger in a CO2 transcritical refrigeration plant using experimental data [J].
Torrella, E. ;
Sanchez, D. ;
Llopis, R. ;
Cabello, R. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (01) :40-49