Numerical Modelling and Sensitivity Analysis of Natural Draft Cooling Towers

被引:2
作者
Dhorat, A. [1 ]
Al-Obaidi, M. A. [1 ,2 ]
Mujtaba, I. M. [1 ]
机构
[1] Univ Bradford, Fac Engn & Informat, Sch Engn, Bradford, W Yorkshire, England
[2] Middle Tech Univ, Baghdad, Iraq
来源
CHEMICAL PRODUCT AND PROCESS MODELING | 2018年 / 13卷 / 04期
关键词
cooling towers; numerical modelling; sensitivity analysis; mass transfer; cost analysis;
D O I
10.1515/cppm-2017-0078
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Cooling towers are a relatively inexpensive and consistent method of ejecting heat from several industries such as thermal power plants, refineries, and food processing. In this research, an earlier model from literature was to be validated across three different case studies. Unlike previous models, this model considers the height of the fill as the discretised domain, which produces results that give it in a distribution form along the height of the tower. As there are limitations with the software used (gPROMS) where differential equations with respect to independent variables in the numerator and denominator cannot be solved, a derivative of the saturation vapour pressure with respect to the temperature of the air was presented. Results shown were in agreement with the literature and a parametric sensitivity analysis of the cooling tower design and operating parameters were undertaken. In this work the height of fill, mass flowrates of water and air were studied with respect to sensitivity analysis. Results had shown large variations in the outlet temperatures of the water and air if the mass flows of water and air were significantly reduced. However, upon high values of either variable had shown only small gains in the rejection of heat from the water stream. With respect to the height of the fill, at larger heights of the fill, the outlet water temperature had reduced significantly. From a cost perspective, it was found that a change in the water flowrate had incurred the largest cost penalty with a 1 % increase in flowrate had increased the average operating cost by 1.2 %. In comparison, a change in air flowrate where a 1 % increase in flowrate had yielded an average of 0.4 % increase in operating cost.
引用
收藏
页数:22
相关论文
共 29 条
[11]   Numerical Modelling of Natural Draft Wet-Cooling Towers [J].
Klimanek, Adam .
ARCHIVES OF COMPUTATIONAL METHODS IN ENGINEERING, 2013, 20 (01) :61-109
[12]  
Kloppers J, 2005, R D J SAIMECHE, V20, P6
[13]  
Kloppers J.C., 2003, THESIS U STELLENBOSC
[14]   A critical investigation into the heat and mass transfer analysis of counterflow wet-cooling towers [J].
Kloppers, JC ;
Kröger, DG .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2005, 48 (3-4) :765-777
[15]   A critical investigation into the heat and mass transfer analysis of crossflow wet-cooling towers [J].
Kloppers, JC ;
Kröger, DG .
NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2004, 46 (08) :785-806
[16]  
Kroger Detlev, 2004, AIR COOLED HEAT EXCH, V2
[17]   Thermal performances investigation of a wet cooling tower [J].
Lemouari, M. ;
Boumaza, M. ;
Mujtaba, I. M. .
APPLIED THERMAL ENGINEERING, 2007, 27 (5-6) :902-909
[18]   Experimental analysis of heat and mass transfer phenomena in a direct contact evaporative cooling tower [J].
Lemouari, M. ;
Boumaza, M. ;
Kaabi, A. .
ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (06) :1610-1617
[19]   Modeling and simulation of counterflow wet-cooling towers and the accurate calculation and correlation of mass transfer coefficients for thermal performance prediction [J].
Llano-Restrepo, Mario ;
Monsalve-Reyes, Robinson .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 74 :47-72
[20]   Cooling limitations in power plants: Optimal multiperiod design of natural draft cooling towers [J].
Martin, Mariano ;
Martin, Monica .
ENERGY, 2017, 135 :625-636