ACCELERATED AGING AND FLASHOVER TESTS ON 138 KV NONCERAMIC LINE POST INSULATORS

被引:78
作者
SCHNEIDER, HM
GUIDI, WW
BURNHAM, JT
GORUR, RS
HALL, JF
LAMPE, WD
FINI, GP
MARRONE, G
PORRINO, A
MCELROY, AJ
机构
[1] ELECT POWER RES INST,PALO ALTO,CA
[2] FLORIDA POWER & LIGHT CO,MIAMI,FL 33101
[3] ARIZONA STATE UNIV,TEMPE,AZ 85287
[4] SWEDISH TRANSMISS RES INST,LUDVIKA,SWEDEN
关键词
NONCERAMIC INSULATORS; ARTIFICIAL AGING; ACCELERATED AGING; LINE POSTS; CLEAN FOG TESTS; AUDIBLE NOISE; RADIO INFLUENCE VOLTAGE;
D O I
10.1109/61.180353
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The behavior of 138 kV nonceramic line post insulators is investigated by means of clean fog tests conducted before and after aging in a specially designed accelerated aging chamber. The laboratory aging cycles are justified on the basis of actual weather in the coastal regions of Florida. Analytical measurements quantifying the degree of artificial aging are discussed and comparisons of artificial aging with service experience are presented. Observations of audible noise and radio influence voltage during the clean fog tests are reported.