DEVELOPMENT OF A MODEL FOR PREDICTING FLICKER FROM ELECTRIC-ARC FURNACES

被引:74
作者
MANCHUR, G
ERVEN, CC
机构
[1] Ontario Hydro, Research Division, 800 Kipling Avenue, Toronto
关键词
VOLTAGE FLUCTUATIONS; FLICKER; ELECTRIC ARC FURNACE; DIGITAL SIGNAL ANALYSIS; ARC FURNACE MODEL;
D O I
10.1109/61.108936
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Owing to the characteristics of electric-arc phenomena electric arc furnace loads can result in serious electrical disturbances on a power system. Low level frequency modulation of the supply voltage of less than 0.5% can cause annoying flicker in lamps and invoke public complaints when the frequency lies in the range of 6-10 Hz. There is a need therefore to develop better techniques to predict flicker effects from single and multiple arc furnace loads and the effects of compensation schemes. This paper discusses the nature of arc furnace loads, and describes the instrumentation, field measurements and signal analysis techniques which were undertaken to develop an arc furnace model. A single phase furnace model is proposed suitable for use on digital simulation programs such as the EMTP or other appropriate commercial software simulation programs. Representative results based on actual furnace input data are included to show the validity of the model.
引用
收藏
页码:416 / 426
页数:11
相关论文
共 2 条
[1]  
ERVEN CC, 1983, ANAL FLICKER ARC FUR
[2]  
MANCHUR G, 1990, DEV MODEL PREDICTING