On-Line PMU-Based Transmission Line Parameter Identification

被引:34
|
作者
Zhao, Xuanyu [1 ]
Zhou, Huafeng [1 ]
Shi, Di [2 ]
Zhao, Huashi [1 ]
Jing, Chaoyang [2 ]
Jones, Chris [2 ]
机构
[1] Control Ctr China So Power Grid CSG, Guangzhou, Guangdong, Peoples R China
[2] eMIT LLC, Pasadena, CA 95117 USA
来源
关键词
Impedance parameters; phasor measurement unit (PMU); transmission line;
D O I
10.17775/CSEEJPES.2015.00021
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
China Southern Power Grid Company (CSG) recently developed and implemented an online PMU-based transmission line (TL) parameter identification system (TPIS). Traditionally, TL parameters are calculated based on transmission tower geometries, conductor dimension, estimates of line length, conductor sags, etc. These parameters only approximate the effect of conductor sag and ignore the dependence of impedance parameters on temperature variation. Recent development in PMU technology has made it possible to calculate TL parameters accurately. The challenges are that such an application requires highly accurate PMU data while the accuracy of PMU measurements under different working/system conditions can be uncertain. With a large number of PMUs widely installed in its system, CSG plans to improve and update the EMS database using the newly developed TPIS. TPIS provides an innovative yet practical problem formulation and solution for TL parameter identification. In addition, it proposes a new metric that can be used to determine the credibility of the calculated parameters, which is missing in the literature. This paper discusses the methodologies, challenges, as well as implementation issues noticed during the development of TPIS.
引用
收藏
页码:68 / 74
页数:7
相关论文
共 50 条
  • [1] PMU-based Line and Transformer Parameter Estimation
    Borda, Carlos
    Olarte, Andres
    Diaz, Hernando
    2009 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION, VOLS 1-3, 2009, : 1453 - 1460
  • [2] A PMU-Based Method for On-Line Thevenin Equivalent Estimation
    Abdi, Pourya
    Hamedani-Golshan, Mohamad-Esmail
    Alhelou, Hassan Haes
    Milano, Federico
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2022, 37 (04) : 2796 - 2807
  • [3] Uncertainty propagation in PMU-based transmission line monitoring
    Tuttelberg, Kaur
    Kilter, Jako
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (03) : 745 - 755
  • [4] On-line Overhead Transmission Line And Transformer Parameters Identification Based On PMU Measurements
    Vicol, Bogdan
    2014 INTERNATIONAL CONFERENCE AND EXPOSITION ON ELECTRICAL AND POWER ENGINEERING (EPE), 2014, : 1045 - 1050
  • [5] On-line Parameter Identification for Excitation System based on PMU Data
    Bi, Tianshu
    Xue, Ancheng
    Xu, Guoyi
    Guo, Xiaolong
    Ge, Fei
    Wang, Zhengfeng
    CRIS: 4TH INTERNATIONAL CONFERENCE ON CRITICAL INFRASTRUCTURE, 2009, : 43 - +
  • [6] A novel PMU-based transmission line protection scheme design
    Khorashadi-Zadeh, Hassan
    Li, Zuyi
    2007 39TH NORTH AMERICAN POWER SYMPOSIUM, VOLS 1 AND 2, 2007, : 13 - 19
  • [7] Synchronized phasor based on-line parameter identification of overhead transmission line
    Bi, Tianshu
    Chen, Jinmeng
    Wu, Jingtao
    Yang, Qixun
    2008 THIRD INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES, VOLS 1-6, 2008, : 1657 - 1662
  • [8] Transmission line parameter identification method based on PMU error correction
    Zhang J.
    Lei J.
    He Y.
    Wu P.
    Yu J.
    Xiang M.
    Ren P.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2022, 50 (19): : 130 - 137
  • [9] Transmission line parameter identification using PMU measurements
    Shi, Di
    Tylavsky, Daniel J.
    Koellner, Kristian M.
    Logic, Naim
    Wheeler, David E.
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2011, 21 (04): : 1574 - 1588
  • [10] Robust classification model for PMU-based on-line power system DSA with missing data
    Zhang, Yuchen
    Xu, Yan
    Dong, Zhao Yang
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (18) : 4484 - 4491