MEASUREMENTS OF DIELECTRIC STRESS IN EHV POWER TRANSFORMER INSULATION

被引:3
|
作者
VAILLES, C
MALEWSKI, R
XUAN, DD
AUBIN, J
机构
[1] ECOLE POLYTECH,MONTREAL,PQ H3C 3A7,CANADA
[2] HYDRO QUEBEC,VARENNES,PQ,CANADA
关键词
D O I
10.1109/61.473383
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A relatively high failure rate of the internal insulation of EHV power transformers has been reported by public utilities. This prompted a study of the safety margin of EHV transformers in service and under test. In this project, a number of transient overvoltages were digitally recorded in EHV substations and the transient voltage distribution along the HV winding was measured digitally on many untanked transformers. With this information, a transient induced at (and across) every disc of the winding by a system generated overvoltage can be calculated and compared to a transient appearing at the same winding section during the impulse test. The pertinence and severity of the standard impulse test can be assessed from this comparison. Subsequently, a dielectric stress in the winding insulation was calculated with the aid of an electric field plotting program. A critically stressed path was then selected in the winding insulation, and a cumulative stress computed along this path: The insulation safety margin was subsequently determined by comparing the cumulative stress to a withstand reference curve for paper-oil insulation. The reference curve for the bulk oil insulation, and for the creep stress along a spacer or barrier was derived from published works. An evaluation of the safety margin indicates that test impulse waveforms specified in the standards do not always represent system-generated transients, which can jeopardize EHV transformer insulation. The insulation can be designed in such a way to keep a similar safety margin in different parts of the winding, and insulating materials can be used more efficiently.
引用
收藏
页码:1757 / 1763
页数:7
相关论文
共 50 条
  • [41] Dielectric measurements on cryogenic insulation systems
    Sumereder, C
    Gerhold, J
    Muhr, M
    Woschitz, R
    PROCEEDINGS OF THE 2002 IEEE 14TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS, 2002, : 225 - 227
  • [42] The Impact of the Use of Dry Lubricating Compound on the Dielectric Properties of Solid and Liquid Insulation of a Power Transformer
    Ramesh, Gopalan
    Sharma, Ashutosh
    Thakkar, Hemang
    2022 7TH INTERNATIONAL ADVANCED RESEARCH WORKSHOP ON TRANSFORMERS (ARWTR 2022), 2022, : 24 - 29
  • [43] Compensating the effect of residual dipole energy on dielectric response for effective diagnosis of power transformer insulation
    Mishra, Deepak
    Baral, Arijit
    Chakravorti, Sivaji
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2018, 12 (03) : 314 - 322
  • [44] Nonlinear Dielectric Properties of the Stator and Transformer Insulation Systems
    Cheng, Jialu
    Taylor, Nathaniel
    Werelius, Peter
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (01) : 240 - 246
  • [45] Transformer Insulation Structure for Dielectric Liquids with Higher Permittivity
    Sbravati, A.
    Rapp, K.
    Schmitt, P.
    Krause, Ch.
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [46] Dielectric diagnosis of water content in transformer insulation systems
    Küchler, A
    Bedel, T
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2001, 11 (01): : 65 - 68
  • [47] Dielectric strength of transformer insulation at DC polarity reversal
    Hasegawa, T
    Yamaji, K
    Hatano, M
    Kouan, T
    Hosokawa, N
    IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (04) : 1526 - 1531
  • [48] Impact of Moisture and Ageing on the Dielectric Response of Transformer Insulation
    Jadav, Raj B.
    Ekanayake, Chandima
    Saha, Tapan K.
    2012 22ND AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC): GREEN SMART GRID SYSTEMS, 2012,
  • [49] Understanding the impacts of moisture and thermal ageing on transformer's insulation by dielectric response and molecular weight measurements
    Saha, T. K.
    Purkait, P.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (02) : 568 - 582
  • [50] An Attempt to Identify Voltage Related Non-Linearities of Transformer Insulation from Dielectric Response Measurements
    Ojha, S. K.
    Purkait, P.
    Chatterjee, B.
    Chakravorti, S.
    2011 IEEE REGION 10 CONFERENCE TENCON 2011, 2011, : 848 - 852