In this study, a concept of using phase change material (PCM) for improving cooling efficiency of an air-conditioner had been presented under Thai climate. Paraffin waxes melting point at around 20 degrees C was selected to evaluate the thermal performance by reducing the air temperature entering the evaporating coil. The model of PCM celluloid balls had been performed with the air-conditioner. Moreover, the mathematical model of the air-conditioner with the PCM storage was developed and verified with the testing results. From the study results, it could be seen that the simulated data agreed quite well with the experimental result at the discrepant around 2-4%. Finally, the model was used to analyze the economic result which was found that the electrical consumption of the modified air-conditioner could be decreased 3.09 kW h/d. The electrical power consumption of the modified unit was 36.27 kW hid at the operating time 15 hid compared with 39.36 kW hid of the normal unit at the operating time 12 hid. The saving cost of the PCM bed could be 9.10% or 170.03 USD and the payback period was 4.15 y. (C) 2014 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:175 / 186
页数:12
相关论文
共 11 条
[1]  
Arkar C, 2005, IEA ECES IA ANNEX 17
[2]  
Chaichana S, 2013, P SEM 6 THAIL REN EN
[3]  
Fieback K, 2005, 8 WORKSH EXP M ANN A
[4]  
Khudhair AM, 2007, P ISES WORLD C 2007
[5]  
Kiatsiriroat T, 2010, P SEM 9 HEAT MASS TR
[6]  
Kiatsiriroat T, 2012, P SEM 3 INT C GREEN
[7]  
Neeper D., 1989, P 14 NAT PASS SOL C
[8]   Thermal dynamics of wallboard with latent heat storage [J].
Neeper, DA .
SOLAR ENERGY, 2000, 68 (05) :393-403
[9]  
Salyer I. O., 1990, P 25 INT EN CONV ENG
[10]   The evaluation of peak shaving by a thermal storage system using phase-change materials in air distribution systems [J].
Yamaha, Motoi ;
Misaki, Shinya .
HVAC&R RESEARCH, 2006, 12 (3C) :861-869