POLLUTED INSULATOR FLASHOVER MODEL FOR AC VOLTAGE

被引:73
作者
GHOSH, PS
CHATTERJEE, N
机构
[1] Department of Electrical Engineering, High Tension Laboratory, Jadavpur University, Calcutta
关键词
D O I
10.1109/94.368688
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Considerable theoretical and experimental research on polluted insulators is yet to yield a perfect generalized mathematical model which can predict accurately critical flashover voltages and currents. In this paper an ac model has been proposed especially applicable to static arcs. The salient features of the proposed model is that it takes into account the appropriate selection of are constants for different chemical nature of the pollutants. The computed results closely follow the experimental curves and can predict rms value of critical flashover voltages with a mean absolute error (MAE) of < 4%. The validity of the model was verified by comparing the computed results of rms critical flashover voltages and currents against experimental and theoretical data of other researchers for a number of practical insulator of different geometries and good agreement has been obtained.
引用
收藏
页码:128 / 136
页数:9
相关论文
共 17 条
  • [1] Rizk A.M., Mathematical Models for Pollution Flashover, Electra, 78, pp. 71-103, (1981)
  • [2] Boeme H., Obenaus F., Pollution Flashover Tests on Insulators in the Laboratory and in Systems and the Model Concept of Creepage-path Flashover, CIGRE, 407, (1966)
  • [3] Alston L.L., Zoledziowski S., Growth of Discharges on Polluted Indulation, Proc. IEE, III, 7, pp. 1260-1266, (1963)
  • [4] Wilkins R., Flashover Voltage of HV Insulators with Uniform Surface Pollution Film, Proc. IEE, 116, 3, pp. 457-465, (1969)
  • [5] Cheng T.C., Dc Interfacial Breakdown on Contaminated Electrolyte Surfaces, IEEE Trans, 19, 6, pp. 536-542, (1984)
  • [6] Gopal S., Rao Y.N., Flashover Phenomenon of Polluted Insulators, Proc. IEE, 131, 4, pp. 140-143, (1984)
  • [7] Calculation of dc and ac Flashover Voltage of Polluted Insulation, IEEE Trans, on Elec. Ins., 25, 4, pp. 723-729, (1990)
  • [8] Rahal A.H., Huraux C., Flashover Mechanism of HV Insulator, IEEE Trans. PAS, 98, 6, pp. 2223-2231, (1979)
  • [9] Matsumoto T., Ishil M., Kawamura T., Opto-electronic Measurement of Partial Arcs on a Contaminated Surface, IEEE Trans. El. Vol. 19, 19, pp. 534-548, (1984)
  • [10] Ghosh P.S., Chakravorti S., Chatterjee N., Pollution Flashover of Electrolytic Surface under Power Frequency High Voltages, IE (India), pp. 180-184, (1992)