IMPROVED OPERATION OF DIFFERENTIAL PROTECTION OF POWER TRANSFORMERS FOR INTERNAL FAULTS

被引:104
作者
LIU, P [1 ]
MALIK, OP [1 ]
CHEN, DS [1 ]
HOPE, GS [1 ]
GUO, Y [1 ]
机构
[1] UNIV CALGARY,DEPT ELECT ENGN,CALGARY T2N 1N4,ALBERTA,CANADA
关键词
DIFFERENTIAL PROTECTION; POWER TRANSFORMERS; INTERNAL FAULTS;
D O I
10.1109/61.156994
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The possibility of non-operation for internal faults of second harmonic restraint differential protection of transformers is studied in this paper. This problem is analyzed using three algorithms for a larger number of faults and energization of a transformer. The sample data used is based on on-line tests of a laboratory transformer. Modified schemes to improve operation for internal faults are presented.
引用
收藏
页码:1912 / 1919
页数:8
相关论文
共 14 条
[1]  
AKIRA Y, 1979, HITACHI COMMENTS, V61
[2]  
DEGENS AJ, 1981, P IEE C, V128, P155
[3]   3-PHASE DIFFERENTIAL RELAY FOR TRANSFORMER PROTECTION [J].
EINVALL, CH ;
LINDERS, JR .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (06) :1971-1980
[4]  
MALIK OP, 1976, WIN IEEE PES M NEW Y, P1
[5]   A MICROCOMPUTER BASED ULTRA-HIGH-SPEED DISTANCE RELAY - FIELD-TESTS [J].
PHADKE, AG ;
HLIBKA, T ;
ADAMIAK, MG ;
IBRAHIM, M ;
THORP, JS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (04) :2026-2036
[6]   DIGITAL-COMPUTER SYSTEM FOR EHV SUBSTATIONS - ANALYSIS AND FIELD-TESTS [J].
PHADKE, AG ;
HLIBKA, T ;
IBRAHIM, M .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1976, 95 (01) :291-301
[7]  
RAHMAN MA, 1982, P IEE C, V129, P79
[8]   A DIGITAL RELAYING ALGORITHM FOR DETECTING TRANSFORMER WINDING FAULTS [J].
SACHDEV, MS ;
SIDHU, TS ;
WOOD, HC .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) :1638-1648
[9]   DESIGN, IMPLEMENTATION AND TESTING OF A MICROPROCESSOR-BASED HIGH-SPEED RELAY FOR DETECTING TRANSFORMER WINDING FAULTS [J].
SIDHU, TS ;
SACHDEV, MS ;
WOOD, HC ;
NAGPAL, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :108-117
[10]  
SIDHU TS, 1992, 1992 IEEE PES WINT M