A FAST TECHNIQUE FOR OUTAGE STUDIES IN POWER-SYSTEM PLANNING AND OPERATION

被引:5
作者
ELARINI, MMM
SOLIMAN, SA
ALKANDARI, AM
机构
[1] Power Systems Research Group, Electrical Engineering Department, College of Technological Studies, PO Box 42325
关键词
CONTINGENCY ANALYSIS; SECURITY ANALYSIS; PERFORMANCE INDEXES; OUTAGE STUDIES;
D O I
10.1016/0378-7796(94)00916-R
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Security monitoring is a fundamental aspect of the operation of power systems. One of the basic tools that dispatchers use to assess the system security is contingency analysis. This program simulates the state of the system after the sudden loss of an element of production or transmission. The DC load flow used in the determination of the performance index (PI) yields only the real power loading of circuits, and ignores the effects of the bus voltage. Therefore, we present an AC active power model in this paper where the effect of the voltage magnitudes is considered. The changes of the coefficient matrix model due to the line outage are directly determined without reconstruction of that matrix or redetermination of its inverse. Then, the postoutage angle is obtained directly. A derivation of the PI is presented, including only the overloaded lines as a result of the fast contingency screening approach proposed in the paper. Real and practical values of the line power limits required for PI calculations are considered. Furthermore, a simple method for the determination of some matrices included in the PI formulation is introduced in this paper to reduce the computation time compared with that for the Wollenberg-Mikolinnas algorithm. The proposed approach is applied to an IEEE 14-node system and the ranking table is obtained. The proposed method was found to be excellent.
引用
收藏
页码:203 / 211
页数:9
相关论文
共 15 条
[1]  
Peterson, Tinney, Bree, Iterative linear AC power flow solution for fast approximation outage studies, IEEE Transactions on Power Apparatus and Systems, pp. 2048-2056, (1972)
[2]  
Stott, Alsac, Fast decoupled load flow, IEEE Transactions on Power Apparatus and Systems, pp. 859-869, (1974)
[3]  
Albuyeh, Bose, Heath, Reactive power consideration in automatic contingency selection, IEEE Transactions on Power Apparatus and Systems, pp. 107-112, (1982)
[4]  
Zaborszky, Whang, Prasad, Fast contingency evaluation using concentric relaxation, IEEE Transactions on Power Apparatus and Systems, pp. 28-36, (1980)
[5]  
Dabbaghchi, Irisarri, AEP automatic contingency selector branch outage impacts on load bus voltage profile, IEEE Transactions on Power Systems, pp. 37-45, (1986)
[6]  
Chen, Bose, Direct ranking for voltage contingency selection, IEEE Trans. Power Syst., 4, pp. 1335-1344, (1989)
[7]  
Ejebe, Van Meeteren, Wollenberg, Fast contingency screening and evaluation for voltage security analysis, IEEE Trans. Power Syst., 3, pp. 1582-1590, (1988)
[8]  
Mohamed, Jasmon, Voltage contingency selection technique for security assessment, IEE Proc. C, 136, pp. 24-28, (1989)
[9]  
Khu, Lauby, Bowen, A fast linearization method to evaluate the effect of circuit contingencies upon system load-bus voltages, IEEE Transactions on Power Apparatus and Systems, pp. 3926-3932, (1982)
[10]  
Sachdev, Ibrahim, A fast approximate technique for outage studies in power system planning and operation, IEEE Transactions on Power Apparatus and Systems, pp. 1133-1142, (1974)