CURRENT TRANSFORMER;
TRANSIENT RESPONSE;
DIGITAL SIMULATION;
EMTP;
D O I:
10.1109/61.277712
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
This paper describes an EPRI study of Current Transformer (CT) digital models intended for protective relay transient performance analysis. Experimental evaluation of CT models implemented using Electro Magnetic Transient Program (EMTP) was carried out. Two relaying CTs with 600/5 and 2000/5 ratios were used in the study. Experiments in a high power laboratory were performed to obtain transient responses. Simulation of the CT response to the same transient events was set up using three different CT models. They were implemented based on the saturable transformer and nonlinear reactor models available in an EMTP. Comparison of laboratory and simulation results indicates that CT models developed based on the EMTP program give satisfactory results for most of the cases. It has also been discovered that in some instances EMTP models need further improvements.