EXPERIMENTAL EVALUATION OF EMTP-BASED CURRENT TRANSFORMER MODELS FOR PROTECTIVE RELAY TRANSIENT STUDY

被引:90
作者
KEZUNOVIC, M
KOJOVIC, L
ABUR, A
FROMEN, CW
SEVCIK, DR
PHILLIPS, F
机构
[1] HOUSTON LIGHTING & POWER,HOUSTON,TX
[2] ELECT POWER RES INST,PALO ALTO,CA 94303
关键词
CURRENT TRANSFORMER; TRANSIENT RESPONSE; DIGITAL SIMULATION; EMTP;
D O I
10.1109/61.277712
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes an EPRI study of Current Transformer (CT) digital models intended for protective relay transient performance analysis. Experimental evaluation of CT models implemented using Electro Magnetic Transient Program (EMTP) was carried out. Two relaying CTs with 600/5 and 2000/5 ratios were used in the study. Experiments in a high power laboratory were performed to obtain transient responses. Simulation of the CT response to the same transient events was set up using three different CT models. They were implemented based on the saturable transformer and nonlinear reactor models available in an EMTP. Comparison of laboratory and simulation results indicates that CT models developed based on the EMTP program give satisfactory results for most of the cases. It has also been discovered that in some instances EMTP models need further improvements.
引用
收藏
页码:405 / 412
页数:8
相关论文
共 13 条
  • [1] FRAME JG, 1982, IEEE TPAS, V101
  • [2] IBERO A, 1990, RGE4 REV GEN EL
  • [3] KEZUNOVIC M, 1992, IEEE T POWER DELIVER, V7
  • [4] KEZUNOVIC M, 1991, IEEE T POWER DELIVER, V6
  • [5] LUCAS JR, 1992, IEEE T POWER DELIVER, V7
  • [6] MARSHALL DE, 1929, CURRENT TRANSFORMER
  • [7] POLJAK M, 1988, IEEE T POWER DELIVER, V3
  • [8] TRANSVERSE INTERFERENCE VOLTAGES ON SECONDARY PROTECTION WIRING AT SUBSTATIONS
    WISZNIEWSKI, A
    MARCZONEK, S
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (01): : 261 - 266
  • [9] WU AY, 1985, IEEE T IND APPLICATI, V21
  • [10] ZOCHOLL SE, 1990, 17TH P ANN W PROT RE