HIGH IMPEDANCE FAULT-TESTS ON THE TAIPOWER PRIMARY DISTRIBUTION-SYSTEM

被引:5
作者
CHU, HY
CHEN, MT
HUANG, CL
CHEN, SL
YEN, SS
机构
[1] Department of Electrical Engineering, National Cheng Kung University, Tainan
[2] Department of Electrical Engineering, National Tsing Hua University, Hsinchu
[3] Power Research Laboratory, Taiwan Power Company, Taipei
关键词
D O I
10.1016/0378-7796(90)90061-7
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High impedance faults on the multigrounded three-phase four-wire primary distribution system cannot be detected effectively by existing overcurrent sensing devices. This paper summarizes some of the staged fault test results of different detection methods applied to the Taipower primary distribution system. The methods include the wiring modification of the ground overcurrent relay, the ground product relay, the ratio ground relay and the harmonic current approach. The test results are reported and discussed for the purpose of providing a practical evaluation of high impedance fault detection. © 1990.
引用
收藏
页码:105 / 114
页数:10
相关论文
共 16 条
[1]  
Blackburn, Kresser, System grounding and protective relaying, Applied Protective Relaying, pp. 11.1-11.12, (1979)
[2]  
Lee, Bishop, Performance testing for the ratio ground relay on a four-wire distribution feeder, IEEE Trans., 102 PAS, pp. 2943-2949, (1983)
[3]  
Carr, Detection of high impedance faults on primary distribution systems, IEEE Trans., 100 PAS, pp. 2008-2016, (1981)
[4]  
Power Technologies, Inc., Detection of high impedance faults, EPRI Research Project 1285-1, Final Rep. EL-2413, (1982)
[5]  
Hughes Aircraft Company, High impedance fault detection using third harmonic currents, EPRI Research Project 1285-2, Final Rep. EL-2430, (1982)
[6]  
Aucoin, Russell, Distribution high impedance fault detection utilizing high frequency current components, IEEE Trans., 101 PAS, pp. 1596-1606, (1982)
[7]  
Graham, Carlson, Granberg, Broken-conductor and high-impedance fault detection by high frequency impedance monitoring, IEEE PES Winter Meeting, (1980)
[8]  
Lee, Kilar, Summary and status report on research to detect and de-energize high impedance faults on three-phase four-wire distribution circuits, IEEE PES Summer Meeting, (1979)
[9]  
Russell, New developments in systems for transmission and distribution substation control and protection, Electr. Power Syst. Res., 5, pp. 21-34, (1982)
[10]  
CWC, Training Inst. of Taiwan Power Co., CWP ground product relay, Protective Relays Handbook, pp. 61-76, (1979)