A CONTRIBUTION ON THE TRACEABILITY OF PARTIAL DISCHARGE MEASUREMENTS

被引:16
作者
OSVATH, P [1 ]
CARMINATI, E [1 ]
GANDELLI, A [1 ]
机构
[1] POLITECN MILAN,DIPARTMENTO ELETTROTECN,I-20133 MILAN,ITALY
来源
IEEE TRANSACTIONS ON ELECTRICAL INSULATION | 1992年 / 27卷 / 01期
关键词
D O I
10.1109/14.123448
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Commercially used partial discharge (PD) detectors are intended to capture current pulses, generated by PD activity in the insulation of a HV test object and then to integrate it, producing a display proportional to the apparent charge. The integration procedure is approximated by a low pass (or band pass) filter and therefore different partial detectors display different charges on the same measurement setup. In the present paper, the error of the approximated integration is simulated and analyzed, and a new calibrator is proposed which has an adjustable duration current pulse. Using the calibrator, the correct working range of the PD detector can be tested and thus qualified. The new calibrator, as a reference unit at Bureau of Standards, can be considered a base of traceability of PD measurement.
引用
收藏
页码:130 / 134
页数:5