THE INFLUENCE OF MOTOR REACCELERATION ON VOLTAGE SAGS

被引:73
作者
BOLLEN, MHJ
机构
[1] Manchester Centre for Electrical Energy, University of Manchester Institute of Science and Technology
关键词
D O I
10.1109/28.395271
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The assumption that a voltage sag is rectangular is not correct in a system with large induction motor toads. The motors decelerate during the short circuit. After fault-clearing they will accelerate again, drawing a high reactive current from the supply, causing a prolonged postfault voltage sag. This is aggravated by the removal of branches by the protection. The resulting shape of some voltage sags in an example system is shown and discussed. For the example system, a stochastic voltage sag table is determined. This table gives the expected number of sags of different depth and duration. The influence of faster protection and of reduced transformer impedance on the table is presented. A simple motor model is implemented in a method for including interruptions due to voltage sags in the reliability analysis of power systems. This model is presented briefly and used to show the influence of motor parameters on the number of sags that lead to an interruption of plant operation.
引用
收藏
页码:667 / 674
页数:8
相关论文
共 8 条
[1]  
BOLLEN MHJ, 1993, EUT93E276 U TECHN FA
[2]  
BOLLEN MHJ, 1993, 28TH IEEE IND APPL S, P1461
[3]   PREDICTING AND PREVENTING PROBLEMS ASSOCIATED WITH REMOTE FAULT-CLEARING VOLTAGE DIPS [J].
CONRAD, L ;
LITTLE, K ;
GRIGG, C .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1991, 27 (01) :167-172
[4]   EFFECTS OF MOMENTARY VOLTAGE DIPS ON THE OPERATION OF INDUCTION AND SYNCHRONOUS MOTORS [J].
DAS, JC .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (04) :711-718
[5]  
EFTHYMIADIS AE, 1993, IPSA USER MANUAL VER
[6]   VOLTAGE INSTABILITIES SUBSEQUENT TO SHORT-CIRCUIT RECOVERIES [J].
ELSADEK, MZ .
ELECTRIC POWER SYSTEMS RESEARCH, 1991, 21 (01) :9-16
[7]  
YALCINKAYA G, 1994, SEP POW ENG C GALW
[8]  
1994, IEEE T IND APPLICAT, V30, P805