DETERMINATION OF INSULATION PARAMETERS OF CURRENT TRANSFORMERS AT MULTIPLE MEASUREMENTS IN MONITORING SYSTEMS UNDER WORKING VOLTAGE

被引:1
作者
Beliaev, V. K. [1 ,2 ]
Panenko, H. N. [3 ]
机构
[1] Sci Ind Enterprise OST, Tech Sci, 33-D Bulvarno Kudryavskaya Str, UA-01054 Kiev, Ukraine
[2] Sci Ind Enterprise OST, 33-D Bulvarno Kudryavskaya Str, UA-01054 Kiev, Ukraine
[3] Natl Tech Univ Ukraine, Kyiv Polytech Inst, 37 Prospect Peremohy, UA-03056 Kiev 56, Ukraine
关键词
high voltage insulation; diagnostics; data processing procedure; processing procedure error; dielectric loss tangent; current transformer;
D O I
10.20998/2074-272X.2016.5.06
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Features of the data processing procedures of multiple measurements of the dielectric loss tangent of the high-voltage insulation, which are based on the comparison method, were considered. Three procedures were compared: the one procedure uses an assignment of a particular standard object for comparison, and two procedures don't use assignments of the special standard objects. Expressions of methodical errors of studied procedures were obtained. Analysis and calculations, which use the obtained expressions were made. Evaluations showed that an influence of a change of the tangent of dielectric loss of one from the monitoring objects on results of estimation of the tangents of other monitoring objects is the distinctive feature of the procedures without assignment of the standard object. Errors of these procedures more than errors of the traditional procedure, with assignment of the standard object. The study demonstrated that procedures without assignment of standard objects lead to difficultly predictable methodological errors, which hinder to estimate the actual value of the loss tangent and to estimate outcomes of the monitoring, by means comparing with allowable values. Moreover, the decrease of estimations of loss tangents of all objects, as a result of occurrence of at least one the object with strongly bad parameters, hides occurrence of other unsuccessful objects with smaller deviations and makes difficult recognition of such deviations at early stages. Improvements in processing techniques which reduce earlier specified errors and reduce the amount of measurements are proposed. The study results are useful in monitoring and diagnostic of basic insulation of current transformers or high-voltage bushings. References 8, tables 1, figures 5.
引用
收藏
页码:40 / 46
页数:7
相关论文
共 8 条
[1]  
[Anonymous], 2006, 401463012006 SOUH MP
[2]  
Beliaev V.K., 2014, B KHARKIV PETRO VASY, P122
[3]  
Beliaev V.K., 2012, ELECT NETWORKS SYSTE, P68
[4]  
Beliaev V.K., 2013, TEKHNICHNA ELEKTRODY, P81
[5]  
Sakhno AA, 2010, ELECTR ENG ELECTROME, P54
[6]  
Shinkarenko G.V., 2012, ELECT NETWORKS SYSTE, P67
[7]  
Stognii B.S., 2010, WORKS I ELECTRODYNAM, P38
[8]  
Svi P. M., 1992, METODY SREDSTVA DIAG