FEASIBLE EIGENVALUE SENSITIVITY FOR LARGE POWER-SYSTEMS

被引:68
作者
SMED, T [1 ]
机构
[1] ROYAL INST TECHNOL,DEPT ELECT POWER SYST,S-10044 STOCKHOLM 70,SWEDEN
关键词
OSCILLATORY STABILITY; EIGENVALUE SENSITIVITY; LARGE; SPARSE; POWER SYSTEM; HVDC;
D O I
10.1109/59.260827
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Traditional eigenvalue sensitivity for power systems requires the formulation of the system matrix, which lacks sparsity. In this paper, a new sensitivity analysis, derived for a sparse formulation, is presented. Variables that are computed as intermediate results in established eigenvalue programs for power systems, but not used further, are given a new interpretation. The effect of virtually any control action can be assessed based on a single eigenvalue-eigenvector calculation. In particular, the effect of active and reactive power modulation can be found as a multiplication of two or three complex numbers. The method is illustrated in an example for a large power system when applied to the control design for an HVDC-link.
引用