IMPROVEMENT OF THE DC VOLTAGE INSULATION EFFICIENCY OF SUSPENSION INSULATORS UNDER CONTAMINATED CONDITIONS

被引:33
作者
NAITO, K
MORITA, K
HASEGAWA, Y
IMAKOMA, T
机构
[1] NGK Insulators Ltd, Jpn
来源
IEEE TRANSACTIONS ON ELECTRICAL INSULATION | 1988年 / 23卷 / 06期
关键词
Contamination Withstand Voltage - DC Fog Insulator - DC Voltage Insulation - HVDC Insulators - Suspension Insulators;
D O I
10.1109/14.16529
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The authors describe the results of the research and development on a suspension-type insulator having a DC contamination withstand voltage 1.25 to 1.3 times higher than that of the standard DC fog insulator, as measured by the fog-withstand or the clean-fog method. Also described are the withstand voltage characteristics of the suspension insulator contaminated with soluble materials and nonuniformly contaminated, simulating natural-field conditions. Design criteria taking these results into account are also discussed.
引用
收藏
页码:1025 / 1032
页数:8
相关论文
共 6 条
[1]   DC FLASHOVER VOLTAGE CHARACTERISTICS OF CONTAMINATED INSULATORS [J].
FUJIMURA, T ;
NAITO, K ;
SUZUKI, Y .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1981, 16 (03) :189-198
[2]   PERFORMANCE OF INSULATORS FOR DIRECT-CURRENT TRANSMISSION-LINE UNDER POLLUTED CONDITION [J].
KINOTO, I ;
FUJUMURA, T ;
NAITO, K .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1973, PA92 (03) :943-949
[3]  
NAITO K, 4TH INT S HIGH VOLT
[4]  
NIGBOR RJ, 1983, CIGRE3383
[5]  
1982, INSULATION UHV TRANS, P320
[6]  
1984, JUN IEEE WORK GROUP