TOWER MODELING FOR LIGHTNING SURGE ANALYSIS USING ELECTROMAGNETIC TRANSIENTS PROGRAM

被引:16
作者
ALMEIDA, ME
DEBARROS, MTC
机构
关键词
INSULATION COORDINATION; LIGHTNING SURGES; TOWER MODELING;
D O I
10.1049/ip-gtd:19941571
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
For economical insulation co-ordination in transmission and substation equipment, it is necessary to accurately predict the lightning surge overvoltage that occurs in an electric power system. The lightning surge response of transmission towers is one of the main factors that influences the magnitude and the waveshape of the surge arriving at a substation. The paper presents a tower model, based on a finite-difference transmission-line model, that can be used with EMTP. Computation results obtained, for a typical double-circuit 500 kV tower, are in good agreement with field test measurements.
引用
收藏
页码:637 / 639
页数:3
相关论文
共 8 条
[1]   Modelling of a transmission tower for lightning-surge analysis [J].
Hara, T ;
Yamamoto, O .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1996, 143 (03) :283-289
[2]   Tower modeling for lightning analysis of. overhead transmission lines [J].
Martinez, JA ;
Castro-Aranda, F .
2005 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS, 1-3, 2005, :1212-1217
[3]   A method of a lightning surge analysis recommended in Japan using EMTP [J].
Ametani, A ;
Kawamura, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :867-875
[4]   Evaluation of line surge arrester failure rate using multipulse lightning stresses [J].
Zanetta, LC .
2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, 2002, :368-368
[5]   Influence of tower modeling on the assessment of backflashover occurrence on transmission lines due to first negative lightning strokes* [J].
Almeida, Frederico S. ;
Silveira, Fernando H. ;
De Conti, Alberto ;
Visacro, Silverio .
ELECTRIC POWER SYSTEMS RESEARCH, 2021, 197
[6]   Modeling Techniques for Lightning Overvoltage Analysis using the Example of Gas Insulated Transmission Lines (GIL) [J].
Goll, F. ;
Witzmann, R. ;
Neumann, C. ;
Imamovic, D. .
2013 IEEE 1ST INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2013, :35-41
[7]   Monte Carlo analysis of wind farm surge arresters risk of failure due to lightning surges [J].
Sarajcev, Petar ;
Vasilj, Josip ;
Goic, Ranko .
RENEWABLE ENERGY, 2013, 57 :626-634
[8]   Failure risk prediction using artificial neural networks for lightning surge protection of underground MV cables [J].
Orille-Fernandez, Angel L. ;
Khalil, Nabil ;
Rodriguez, Santiago Bogarra .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1278-1282