Impact Factors in Calibration and Application of Field Mill for Measurement of DC Electric Field with Space Charges

被引:23
作者
Zhang, Bo [1 ]
Wang, Wenzhuo [2 ]
He, Jinliang [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
[2] China State Grid Corp, NW Branch, Xian 710048, Shaanxi, Peoples R China
关键词
Calibration; electric field; field meter; measurement; space charge;
D O I
10.17775/CSEEJPES.2015.00032
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The DC electric field is sometimes accompanied by space charges caused by the partial discharge in the air, which impacts DC electric field measurements. This paper describes the impact factors in the calibration and application of the field mill for measuring the DC electric field with space charges. First, the influence of the space charges on calibration results is evaluated and discussed. Then, both the impact of the height of the meter probe above the ground and the touch resistance between the ground and the meter on the measurement results are investigated. Correct calibration and application methods are presented. The results are expected to be of use to engineers for conducting accurate measurements of the DC electric field with space charges.
引用
收藏
页码:31 / 36
页数:6
相关论文
共 20 条
[1]  
[Anonymous], 2271990 IEEE
[2]   2 NEW DESIGNS OF FIELD MILL TYPE FIELDMETERS NOT REQUIRING EARTHING OF ROTATING CHOPPER [J].
CHUBB, JN .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (06) :1178-1181
[3]   Impact Factors in Measurements of Ion-Current Density Produced by High-Voltage DC Wire's Corona [J].
Fang, Chao ;
Cui, Xiang ;
Zhou, Xiangxian ;
Lu, Tiebing ;
Zhen, Yongzan ;
Li, Xuebao .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (03) :1414-1422
[4]   Design, Modeling, and Test of a System for Atmospheric Electric Field Measurement [J].
Fort, Ada ;
Mugnaini, Marco ;
Vignoli, Valerio ;
Rocchi, Santina ;
Perini, Federico ;
Monari, Jader ;
Schiaffino, Marco ;
Fiocchi, Franco .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2011, 60 (08) :2778-2785
[5]   Measurements of power system voltages using remote electric field monitoring [J].
Gerrard, CA ;
Gibson, JR ;
Jones, GR ;
Holt, L ;
Simkin, D .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1998, 145 (03) :217-224
[6]   DC ELECTRIC-FIELD METER WITH FIBEROPTIC READOUT [J].
JOHNSTON, AR ;
KIRKHAM, H ;
ENG, BT .
REVIEW OF SCIENTIFIC INSTRUMENTS, 1986, 57 (11) :2746-2753
[7]   Electric Field and Ion Current Environment of HVdc Transmission Lines: Comparison of Calculations and Measurements [J].
Maruvada, P. Sarma .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (01) :401-410
[8]  
Maruvada P. Sarma, 2000, CORONA PERFORMANCE H
[9]   DEVELOPMENT OF FIELD-MILL INSTRUMENTS FOR GROUND-LEVEL AND ABOVE-GROUND ELECTRIC-FIELD MEASUREMENT UNDER HVDC TRANSMISSION-LINES [J].
MARUVADA, PS ;
DALLAIRE, RD ;
PEDNEAULT, R .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (03) :738-744
[10]   GENERATION AND MEASUREMENT OF DC ELECTRIC-FIELDS WITH SPACE-CHARGE [J].
MISAKIAN, M .
JOURNAL OF APPLIED PHYSICS, 1981, 52 (05) :3135-3144