Numerical Study of the Effect of Different Transverse Fire Locations on Smoke Mass Flow Rate in Tunnel Fires

被引:0
作者
Rongfang Chen
Zhiguo Guo
Yangpeng Liu
Yurun Yang
Qinglan Tan
机构
[1] Jiangxi University of Science and Technology,School of Emergency Management and Safety Engineering
[2] Zhejiang University,State Key Laboratory of Clean Energy Utilization
[3] Huzhou Institute of Zhejiang University,undefined
来源
Fire Technology | 2023年 / 59卷
关键词
Tunnel fires; Transverse fire locations; Mass flow rate; Smoke transport characteristics; Fire dynamics simulator;
D O I
暂无
中图分类号
学科分类号
摘要
Wall restriction is an important factor affecting flame space development, air entrainment and heat transfer. To investigate the smoke characteristics in the one-dimensional horizontal spreading stage at different transverse fire locations in tunnel, FDS was used to simulate and analyze the smoke mass flow rate. The results show that the average smoke mass flow rate is positively correlated with distance from fire source to sidewall and heat release rate (HRR). The maximum smoke temperature rises decay exponentially along the longitudinal direction of the tunnel. Based on dimensional analysis, a prediction model is proposed to predict the average smoke mass flow rate in one-dimensional horizontal spreading stage in tunnel. For wall fires, predicted mass flow rate is 1.29 times of Zukoski model via generalizing the "mirror" effect. For non-wall fires, the dimensionless smoke mass flow is proportional to the 0.19 power of the dimensionless HRR. Besides, the reliability of the prediction model is verified by comparing with full-scale and reduced-scale experiments.
引用
收藏
页码:2567 / 2586
页数:19
相关论文
共 234 条
[31]  
Wang J(2022)Research on the smoke mass flow rate in one-dimensional spreading stage in tunnel with multiple fire sources Case Stud Therm Eng 31 1468-1483
[32]  
Ding Y(2021)Theoretical and numerical study on mass flow rates of smoke exhausted from short vertical shafts in naturally ventilated urban road tunnel fires Tunn Undergr Space Technol 111 2844-2855
[33]  
Gannouni S(2021)Influence of longitudinal ventilation on the mass flow rate distribution of fire smoke flow in tunnels Tunn Undergr Space Technol 112 531-542
[34]  
BenMaad R(2015)Experimental study on the influence of different Fire Technol 51 22-36
[35]  
Feng X(2021)Effect of sidewall on the flame extension characteristics beneath a ceiling induced by carriage fire in a channel Combust Flame 223 1-339
[36]  
Jiang Z(2015)Experimental study on the influence of different transverse fire locations on the critical longitudinal ventilation velocity in tunnel fires Fire Technol 51 71-74
[37]  
Zhang G(2007)Experimental studies on fire-induced buoyant smoke temperature distribution along tunnel ceiling Build Environ 42 13-20
[38]  
Luo X(1981)The flow of fire gases under a beamed ceiling Combust Flame 43 1314-1319
[39]  
Zeng F(2017)Studies on ceiling maximum thermal smoke temperature and longitudinal decay in a tunnel fire with different transverse gas burner locations Appl Therm Eng 110 1-10
[40]  
Chang X(2016)Velocity and temperature attenuation of a ceiling-jet along a horizontal tunnel with a flat ceiling and natural ventilation Tunn Undergr Space Technol 56 13-24