Experimental Study on Burning Characteristics of the Large-Scale Transformer Oil Pool Fire with Different Extinguishing Methods

被引:0
作者
Chuanping Wu
Tiannian Zhou
Baohui Chen
Yu Liu
Ping Liang
机构
[1] State Key Laboratory of Disaster Prevention and Reduction for Power Grid Transmission and Distribution Equipment,
[2] State Grid Hunan Electric Company Limited Disaster Prevention and Reduction Center,undefined
来源
Fire Technology | 2021年 / 57卷
关键词
Pool fire; Transformer oil; Extinguishing; Burning characteristics; Movable extinguishment platform;
D O I
暂无
中图分类号
学科分类号
摘要
In this study, a 100 m2 steel tank was used to simulate transformer oil fires, with an aim of investigating the burning characteristics of a large-scale pool fire. To recover a real thermal state of transformer oil in operation, a heating system was employed to raise the initial fuel temperature. In total, three fire-extinguishing tests were performed using two delivery methods, i.e., a hand-held fire water branch (FWB) and fire water monitor (FWM) to understand their performance in fighting large-scale pool fires. The extinguishing activities using the FWB method were conducted by four trained firefighters, and the FWM was operated by a trained firefighter. Also, a sequence of bench-scale tests was conducted to investigate the impact of initial fuel temperature on the mass burning rate of transformer oil pool fires. This part is a supplement to the large-scale tests. The results demonstrated that the temperatures adjacent to the tank border were reduced as the vertical height increased. The growth rate of the flame height was enhanced in the development stage when the initial fuel temperature was pre-heated to a higher value. Meanwhile, it was found that the burning rate of transformer oil pool fire occurred a slight increase with the initial fuel temperature was grown according to the bench-scale data, while the impact of initial temperature was limited within the tested temperature range. In addition, it was shown that the FWB and FWM were both effective for fighting a large-scale transformer oil pool fire. However, their efficiency was influenced significantly by the concentration of the extinguishing agents and the application density of delivery. In contrast, the FWM might be a good choice when considering the safety of firefighters, because its delivery range is greater and extinguishing time is shorter as compared to the FWB. Here, it shall be noted that the FWM has also its flipsides. Sometimes, the application of a single FWM is not well to extinguish the corner fire or other fire types, in such cases, the FWM strategy should be to use two or more fire trucks in order to cover the whole accident pool.
引用
收藏
页码:461 / 481
页数:20
相关论文
共 81 条
[1]  
Duarte D(2004)A performace overview about fire risk management in the Brazilian hydroelectric generating plants and transmission network J Loss Prev Process Ind 17 65-75
[2]  
Muñoz M(2004)Analysis of the geometric and radiative characteristics of hydrocarbon pool fires Combust Flame 139 263-277
[3]  
Arnaldos J(2007)Predicting the emissive power of hydrocarbon pool fires J Hazard Mater 144 725-729
[4]  
Casal J(2018)Effect of tank diameter on thermal behavior of gasoline and diesel storage tanks fires J Hazard Mater 342 544-552
[5]  
Planas E(1997)Pool fires of transformer oil sinking into a rock bed Fire Saf J 28 33-46
[6]  
Munoz M(1996)Unsteady burning rates of small pool fires Bull Jpn Assoc Fire Sci Eng 45 19-25
[7]  
Planas E(2011)Initial fuel temperature effects on burning rate of pool fire J Hazard Mater 188 369-374
[8]  
Ferrero F(2015)Experimental investigation of foam spread and extinguishment of the large-scale methanol pool fire J Hazard Mater 287 87-92
[9]  
Casal J(2018)The burning rate of n-heptane pool fires with constraint effect beneath an arced ceiling Fuel 233 825-833
[10]  
Leite RM(2018)Experimental study of liquid fuel boilover behavior in normal and low pressures Fire Mater 42 843-858