Developing a Procedure for Segmenting Meshed Heat Networks of Heat Supply Systems without Outflows

被引:2
|
作者
Tokarev V.V. [1 ]
机构
[1] Melent’ev Institute of Energy Systems, Siberian Branch, Russian Academy of Sciences, Irkutsk
基金
俄罗斯基础研究基金会;
关键词
flow distribution; heat network; heat supply; hydraulic power; segmentation; thermal–hydraulic operating mode;
D O I
10.1134/S0040601518060101
中图分类号
学科分类号
摘要
The heat supply systems of cities have, as a rule, a ring structure with the possibility of redistributing the flows. Despite the fact that a ring structure is more reliable than a radial one, the operators of heat networks prefer to use them in normal modes according to the scheme without overflows of the heat carrier between the heat mains. With such a scheme, it is easier to adjust the networks and to detect and locate faults in them. The article proposes a formulation of the heat network segmenting problem. The problem is set in terms of optimization with the heat supply system’s excessive hydraulic power used as the optimization criterion. The heat supply system computer model has a hierarchically interconnected multilevel structure. Since iterative calculations are only carried out for the level of trunk heat networks, decomposing the entire system into levels allows the dimensionality of the solved subproblems to be reduced by an order of magnitude. An attempt to solve the problem by fully enumerating possible segmentation versions does not seem to be feasible for systems of really existing sizes. The article suggests a procedure for searching rational segmentation of heat supply networks with limiting the search to versions of dividing the system into segments near the flow convergence nodes with subsequent refining of the solution. The refinement is performed in two stages according to the total excess hydraulic power criterion. At the first stage, the loads are redistributed among the sources. After that, the heat networks are divided into independent fragments, and the possibility of increasing the excess hydraulic power in the obtained fragments is checked by shifting the division places inside a fragment. The proposed procedure has been approbated taking as an example a municipal heat supply system involving six heat mains fed from a common source, 24 loops within the feeding mains plane, and more than 5000 consumers. Application of the proposed segmentation procedure made it possible to find a version with required hydraulic power in the heat supply system on 3% less than the one found using the simultaneous segmentation method. © 2018, Pleiades Publishing, Inc.
引用
收藏
页码:400 / 409
页数:9
相关论文
共 32 条