Development of a pollution flashover model for 11 kV porcelain and silicon rubber insulator by using COMSOL multiphysics

被引:0
作者
Apu Banik
Abhik Mukherjee
Sovan Dalai
机构
[1] Stamford University Bangladesh,Department of Electrical Engineering
[2] Jadavpur University,undefined
来源
Electrical Engineering | 2018年 / 100卷
关键词
Contaminated insulators; Finite element method; Flashover; Hydrophobic classes; Arc constants;
D O I
暂无
中图分类号
学科分类号
摘要
The reliable operation of transmission line depends on the condition of insulators. The condition of the insulator depends on the pollutants deposited on the surface of the insulator. Prediction of flashover voltage at different conditions is an important task in order to judge the health condition of insulators. Investigating the performance of insulator at every contamination level by experimental process is time consuming. So development of a precise simulation model is very important to predict various flashover performances. In this paper, a finite element method based approach has been proposed to develop a simulation model, which is mainly based on arc Obenaus model and Hapmton criteria. Finite element method analysis has been done by using COMSOL multiphysics software and MATLAB. To conduct the experimental and simulation study, two different types of insulator are used. Different temperature, pollution levels and hydrophobic classes are considered during flashover simulation technique. With the help of AR model leakage current, the residual resistance of the porcelain insulator has been determined. It has been found that arc constants are the most important factors for different types of insulator. Arc constants for the silicon rubber insulator are also determined in the present work to facilitate the simulation model. To validate the model simulation, results are compared with practical results obtained from laboratory experiment.
引用
收藏
页码:533 / 541
页数:8
相关论文
共 28 条
[1]  
Dhahbi-Mergriche N(1997)A new proposal model for flashover of polluted insulators J Phys 30 889-894
[2]  
Beroual A(2004)A new flashover dynamic model of polluted HV insulators IEEE Trans Dielectr Electr Insulation 11 577-584
[3]  
Karhenbuhl L(1969)Flashover voltage of high voltage insulator with uniform surface pollution films Proc IEE 116 457-465
[4]  
Aydogmus Z(1981)Mathematical models for pollution flashover Electra 78 71-103
[5]  
Cebeci M(1978)Flashover characteristics of polluted insulators IE (I) J EL 58 195-2260
[6]  
Wilkins R(1970)Application of dimensional analysis to flashover characteristics ofpolluted insulators Proc IEE 117 2257-1131
[7]  
Rizk FAM(1973)Howto choose insulators for polluted areas IEEE Trans Power Appar Syst 92 1121-06
[8]  
Chatterje N(1981)Analytical estimation of flashover performances of polluted insulators MADRAS 1 01-132
[9]  
Rizk FA(1994)Effect of insulator profiles on DC flashover voltage under polluted conditions. A study using a dynamic arc model IEEE Trans Dielectr Electr Insulation 1 124-289
[10]  
Claverie P(2000)Flashover dynamic model of polluted insulators under AC voltage IEEE Trans Dielectr Electr Insulation 7 283-1921