FEM Simulation and Test Verification of PD Ultrasonic Signal Propagation in a Power Transformer Model

被引:0
作者
Zan Wang
Chaofei Gao
Liwei Zheng
Jikun Ren
Wei Wang
Yushuai Zhang
Shijie Han
机构
[1] North China Electric Power University,State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources
[2] Beijing Information and Technology University,School of Automation
[3] Gaoyi Power Supply Company,undefined
[4] State Grid Hebei Provincial Power Crop,undefined
来源
Journal of Electrical Engineering & Technology | 2021年 / 16卷
关键词
Power transformers; Partial discharge; FEM; Propagation property;
D O I
暂无
中图分类号
学科分类号
摘要
Ultrasonic signals will be generated when partial discharge occurs in internal insulation faults in large oil immersed power transformers: because the ultrasonic signal has strong anti-interference ability and has no direct electromagnetic contact with the equipment, it is widely used in transformer fault detection and positioning. In this paper, the finite element method (FEM) is used to simulate the ultrasonic signal in a 35 kV power transformer. The influence of transformer case on ultrasonic signal propagation is considered, and the propagation law of the ultrasonic signal inside the transformer is obtained. Fabry–Pérot (F–P) fibre acoustic sensors with a centre frequency of 28 kHz were fabricated. A partial discharge detection test was carried out in a 35 kV transformer winding model using the F–P sensors. The test results show that the ultrasonic waveform detected by the F–P sensors are in good agreement with the simulation results, and the propagation of the ultrasonic wave inside the transformer is verified. It lays a foundation for detecting and locating PDs in power transformer by F–P acoustic sensors.
引用
收藏
页码:449 / 457
页数:8
相关论文
共 56 条
  • [1] Bartnikas R(2002)Partial discharges. Their mechanism, detection and measurement IEEE Trans Dielectr Electr Insul 9 763-808
  • [2] Li S(2017)Condition monitoring and diagnosis of power equipment: review and prospective IET High Voltage 2 82-91
  • [3] Li J(2017)Identification and localization of PD-sources in power-transformers and power-generators IEEE Trans Dielectr Electr Insul 24 17-30
  • [4] Fuhr J(2015)Study of improved RSS algorithm for ultrasonic array applied to PD location in transformer IEEE Sens J 15 4986-4991
  • [5] Thomas A(2017)Denoising different types of acoustic partial discharge signals using power spectral subtraction IET High voltage 3 44-50
  • [6] Yongfen L(2013)Location of partial discharge in transformer oil using circular array of ultrasonic sensors IEEE Trans Dielectr Electr Insul 20 1683-1690
  • [7] Fei D(2018)Localization of partial discharge in transformer oil using Fabry-Pérot optical fiber sensor array IEEE Trans Dielectr Electr Insul 25 2279-2286
  • [8] Wei P(2009)Study of propagation behaviour of Partial Discharge acoustic signals in a 3-D model tank. 44th International Universities Power Engineering Conference (UPEC) Glasgow 2009 1-5
  • [9] Hussein R(2012)Optimization of single-/multi-/single-mode intrinsic Fabry-Perot fiber sensors J Lightwave Technol 30 2281-2288
  • [10] Shaban K(2012)A methodology for identification and localization of partial discharge sources using optical sensors IEEE Trans Dielectr Electr Insul 19 18-28