A wavelet packet based method for adaptive single-pole auto-reclosing

被引:0
作者
Sadegh Jamali
Navid Ghaffarzadeh
机构
[1] Iran University of Science and Technology,Centre of Excellence in Power Systems Automation and Operation
来源
Journal of Zhejiang University SCIENCE C | 2010年 / 11卷
关键词
Adaptive auto-reclosing; Arcing faults; Permanent faults; Transmission lines; Wavelet packet transform; TM762.2;
D O I
暂无
中图分类号
学科分类号
摘要
We present a new algorithm for adaptive single-pole auto-reclosing of power transmission lines using wavelet packet transform. The db8 wavelet packet decomposes the faulted phase voltage waveform to obtain the coefficients of the nodes 257, 259 to 262. An index is then defined from the sum of the energy coefficients of these nodes. By evaluating the index, transient and permanent faults, as well as the secondary arc extinction instant, can be identified. The significant advantage of the proposed algorithm is that it does not need a threshold level and therefore its performance is independent of fault location, line parameters, and operating conditions. Moreover, it can be used in transmission lines with reactor compensation. The proposed method has been successfully tested under a variety of fault conditions on a 400 kV overhead line of the Iranian National Grid using the Electro-Magnetic Transient Program (EMTP). The test results validated the algorithm’s ability in distinguishing between transient arcing and permanent faults and determining the instant of secondary arc extinction.
引用
收藏
页码:1016 / 1024
页数:8
相关论文
共 58 条
  • [1] Aggarwal R.K.(1994)Neural-network based adaptive single-pole autoreclosure technique for EHV transmission systems IEE Proc.-Gener. Transm. Distr. 141 155-160
  • [2] Johns A.T.(2001)An alternative approach to adaptive single pole auto-reclosing in high voltage transmission systems based on variable dead time control IEEE Trans. Power Del. 16 676-686
  • [3] Song Y.H.(1980)Evaluation of the effect of power circuit breaker reclosing practices on turbine-generator shafts IEEE Trans. Power Appar. Syst. 99 1764-1779
  • [4] Dunn R.W.(2007)An adaptive single pole autoreclosure based on zero sequence power Electr. Power Syst. Res. 77 438-446
  • [5] Fitton D.S.(1996)Design and implementation of an adapative single pole autoreclosure technique for transmission lines using artificial neural networks IEEE Trans. Power Del. 11 748-755
  • [6] Ahn S.P.(1989)Prediction methods for preventing single-phase reclosing on permanent fault IEEE Trans. Power Del. 4 114-121
  • [7] Kim C.H.(2010)New approach to adaptive single pole auto-reclosing of power transmission lines IET Gener. Transm. Distr. 4 115-122
  • [8] Aggarwal R.K.(1994)Improved technique for modelling fault arcs on faulted EHV transmission systems IEE Proc.-Gener. Transm. Distr. 141 148-154
  • [9] Johns A.T.(2004)The study on single-pole adaptive reclosure of EHV transmission lines with the shunt reactor Proc. CSEE 24 52-56
  • [10] Bowler C.E.J.(1998)Method of Distinguishing Between Instant and Permanent Faults of Transmission Lines Based on Fuzzy Decision IEEE Int. Conf. on Energy Management and Power Delivery 2 445-460