Numerical simulation of heat transfer performance of an air-cooled steam condenser in a thermal power plant

被引:0
作者
Xiufeng Gao
Chengwei Zhang
Jinjia Wei
Bo Yu
机构
[1] Xi’an Jiaotong University,State Key Laboratory of Multiphase Flow in Power Engineering
[2] China University of Petroleum (Beijing),Beijing Key Laboratory of Urban Oil and Gas Distribution Technology
来源
Heat and Mass Transfer | 2009年 / 45卷
关键词
Steam Turbine; Heat Transfer Performance; Wake Zone; Natural Wind; Ambient Wind Speed;
D O I
暂无
中图分类号
学科分类号
摘要
Numerical simulation of the thermal-flow characteristics and heat transfer performance is made of an air-cooled steam condenser (ACSC) in a thermal power plant by considering the effects of ambient wind speed and direction, air-cooled platform height, location of the main factory building and terrain condition. A simplified physical model of the ACSC combined with the measured data as input parameters is used in the simulation. The wind speed effects on the heat transfer performance and the corresponding steam turbine back pressure for different heights of the air-cooled platform are obtained. It is found that the turbine back pressure (absolute pressure) increases with the increase of wind speed and the decrease of platform height. This is because wind can not only reduce the flowrate in the axial fans, especially at the periphery of the air-cooled platform, due to cross-flow effects, but also cause an air temperature increase at the fan inlet due to hot air recirculation, resulting in the deterioration of the heat transfer performance. The hot air recirculation is found to be the dominant factor because the main factory building is situated on the windward side of the ACSC.
引用
收藏
页码:1423 / 1433
页数:10
相关论文
共 35 条
[1]  
Duvenhage K(1996)Flow distortions at the fan inlet of forced-draught air-cooled heat exchangers Appl Therm Eng 16 741-752
[2]  
Vermeulen JA(1996)The influence of wind on the performance of forced draught air-cooled heat exchanger J Wind Eng Ind Aerodyn 62 259-277
[3]  
Meyer CJ(2001)A laboratory simulation of plume dispersion in stratified atmospheres over complex terrain J Wind Eng Ind Aerodyn 89 1-15
[4]  
Kroger DG(2003)Numerical simulations of wind measurements at Amsterdam Airport Schipol J Wind Eng Ind Aerodyn 91 1215-1223
[5]  
Duvenhage K(1972)Hot air circulation by air coolers Chem Eng Prog 68 49-80
[6]  
Kroger DG(2008)CFD simulation on a thermal power plant with air-cooled heat exchanger system in north China Int J Comput Aided Eng Softw 25 342-365
[7]  
Liu HP(2005)Wind tunnel simulation on re-circulation of air-cooled condensers of a power plant J Wind Eng Ind Aerodyn 93 509-520
[8]  
Zhang BY(2006)Numerical investigation of fan performance in a forced draft air-cooled heat exchangers Appl Therm Eng 26 846-852
[9]  
Sang JG(1995)Plume recirculation in mechanical draught heat exchangers Heat Transf Eng 16 42-49
[10]  
Cheng Andrew YS(2001)Enhance air-cooled heat exchanger performance Hydrocarbon Process 80 49-55