Development of hybrid loop heat pipe using pump assistance for cooling application on high heat flux device

被引:0
|
作者
Iwan Setyawan
Nandy Putra
Imansyah Ibnu Hakim
Ridho Irwansyah
机构
[1] Universitas Indonesia,Applied Heat Transfer Research Group, Department of Mechanical Engineering
[2] Kampus UI,Department of Mechanical Engineering
[3] Gunadarma University,undefined
关键词
Dry-out; High heat flux; Hybrid loop heat pipe; Start-up;
D O I
暂无
中图分类号
学科分类号
摘要
Loop heat pipe (LHP) is an effective two-phase heat transfer device that utilizes evaporation and condensation of a working fluid. LHP is widely used in a passive cooling system, highly reliable and a very high thermal conductive device. However, extreme power density can cause dry-out in the evaporator section of LHP and might hinder the performance of the cooling system. The purpose of this research is to design and manufacture a new prototype of LHP by modifying the conventional LHP. The modification was performed by adding a diaphragm pump, called hybrid loop heat pipe (HLHP). The experimental results show that the installation of pumps in the modified LHP was able to prevent the occurrence of a dry out and reduce the operating temperature. Under a constant conductance mode, the pump was activated for 20 minutes and succeded in forcing the system to a new stable condition with a significant temperature drop. These results indicate that HLHP is very promising as a two-phase cooling system that can be proposed for devices that produce high heat flux.
引用
收藏
页码:3685 / 3694
页数:9
相关论文
共 50 条
  • [21] Development and investigation of a loop heat pipe at a high concentration of heat load
    Chernysheva, M. A.
    Vershinin, S. V.
    Maydanik, Y. F.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 197
  • [22] Visualization Research on Heat Pipe Radiator in Cooling Electronic Apparatus with High Heat Flux
    Zhao, Zhongchao
    Ye, Rui
    Chen, Yuping
    Zhou, Genming
    VIBRATION, STRUCTURAL ENGINEERING AND MEASUREMENT I, PTS 1-3, 2012, 105-107 : 1880 - 1884
  • [23] Design, fabrication, investigation and analysis of a novel flat evaporator loop heat pipe for cooling high heat flux server chips
    Xiong, Kangning
    Meng, Like
    Wang, Shuangfeng
    APPLIED THERMAL ENGINEERING, 2022, 201
  • [24] Investigation of a loop heat pipe to achieve high heat flux by incorporating flow boiling
    Liu, Lei
    Yuan, Bo
    Cui, Chenyi
    Yang, Xiaoping
    Wei, Jinjia
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 195
  • [25] Distribution of heat flux by working fluid in loop heat pipe
    Nemec, Patrik
    Malcho, Milan
    EFM15 - EXPERIMENTAL FLUID MECHANICS 2015, 2016, 114
  • [26] Loop heat pipe technology for electronics cooling
    Khrustalev, D
    2001 HD INTERNATIONAL CONFERENCE ON HIGH-DENSITY INTERCONNECT AND SYSTEMS PACKAGING, PROCEEDINGS, 2001, 4428 : 375 - 380
  • [27] Experimental Study on a Pump Driven Loop-Heat Pipe for Data Center Cooling
    Zhang, Shuang
    Ma, Guoyuan
    Zhou, Feng
    JOURNAL OF ENERGY ENGINEERING, 2015, 141 (04)
  • [28] Development and investigation of a loop heat pipe with a high heat-transfer capacity
    Maydanik, Y.
    Pastukhov, V.
    Chernysheva, M.
    APPLIED THERMAL ENGINEERING, 2018, 130 : 1052 - 1061
  • [29] Loop heat pipe for cooling of high-power electronic components
    Vasiliev, Leonid
    Lossouarn, David
    Romestant, Cyril
    Alexandre, Alain
    Bertin, Yves
    Piatsiushyk, Yauheni
    Romanenkov, Vladimir
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2009, 52 (1-2) : 301 - 308
  • [30] High heat flux loop heat pipes
    North, MT
    Sarraf, DB
    Rosenfeld, JH
    Maidanik, YF
    Vershinin, S
    SIXTH EUROPEAN SYMPOSIUM ON SPACE ENVIRONMENTAL CONTROL SYSTEMS, VOLS 1 AND 2, 1997, 400 : 371 - 376