Experimental Investigation of the Effect of Fire Protection Lobby on Stair Pressurization System in a High-Rise Building

被引:0
|
作者
Busra Hepguzel Acikyol
Gokhan Balik
Abdurrahman Kilic
机构
[1] Istanbul Technical University,Faculty of Mechanical Engineering
[2] Etik Muhendislik Danismanlik Tasarim ve Egitim Hizmetleri Ltd. Sti.,undefined
来源
Fire Technology | 2017年 / 53卷
关键词
Stair pressurization; High-rise building; Fire protection lobby; Non-pressurized vestibule;
D O I
暂无
中图分类号
学科分类号
摘要
In this study, the stair pressurization system in a 40-storey high office building in Istanbul is investigated through field tests, in order to understand the effect of the presence of a non-pressurized vestibule (fire protection lobby, FPL) before entering the stair at each floor. The building without FPL is simulated by keeping only one of the two doors (of the stair and FPL) open at each floor. This method gave an opportunity to fix other parameters affecting the stair pressurization system and check solely the effect of FPL. Two different cases are taken into account, where the first one (all doors closed) analyses the condition that all stair doors are kept closed and the second one (critical doors are open) is conducted when the stairwell is opened to the floor on a given level (fire floor) and the stair termination door at the discharge floor is kept open. For both cases, the availability of the FPL is investigated by using the aforementioned arrangement. Under the conditions with approximately the same pressurized air flow rate at all doors closed condition, it is found that the availability of FPL increases the pressure difference between the stairwell and the corridor by a factor of approximately 2.2. This is also justified by using empirical formulations available in literature, where this ratio is calculated as 2.0. The results of this study showed that the FPL arrangement improves the effectiveness of pressurization system in a very high-rise building, despite some tolerable drawbacks.
引用
收藏
页码:135 / 151
页数:16
相关论文
共 50 条
  • [32] PATTON REPORT - FIRE SAFETY FOR HIGH-RISE BUILDING
    PATTON, RM
    ASHRAE JOURNAL, 1971, 13 (04): : 39 - &
  • [33] Fire protection of steel structures in high-rise buildings
    Hochstim, Adolf R.
    Construction Specifier, 2002, 55 (09): : 51 - 54
  • [34] Fire and Smoke Protection Measures for High-Rise Buildings
    Murakami, Suminao
    Murosaki, Yoshiteru
    JOURNAL OF DISASTER RESEARCH, 2011, 6 (06) : 629 - 643
  • [35] The Construction of High-Rise Building Fire Escape Scene
    Qin, Hua
    Gao, Xiao-Tong
    PROCEEDINGS OF THE 20TH CONGRESS OF THE INTERNATIONAL ERGONOMICS ASSOCIATION (IEA 2018), VOL V: HUMAN SIMULATION AND VIRTUAL ENVIRONMENTS, WORK WITH COMPUTING SYSTEMS (WWCS), PROCESS CONTROL, 2019, 822 : 189 - 194
  • [36] BUILDING COMMISSIONERS VIEW OF HIGH-RISE FIRE SAFETY
    FITZGERA.JF
    ASHRAE JOURNAL, 1971, 13 (12): : 34 - &
  • [37] An Optimization of Intelligent Fire Alarm System for High-Rise Building Based on ANASYS
    Liu Keding
    INTELLIGENCE COMPUTATION AND EVOLUTIONARY COMPUTATION, 2013, 180 : 415 - 421
  • [38] FIELD CHECKS ON BUILDING PRESSURIZATION FOR SMOKE CONTROL IN HIGH-RISE BUILDINGS.
    Tamura, G.T.
    Shaw, C.Y.
    ASHRAE Journal, 1981, 23 (02) : 21 - 25
  • [39] Full-scale experimental and numerical simulation of fire in a High-rise Residential Building
    Yang, Juntao
    Yang, Yun
    Liang, Jing
    ADVANCES IN INDUSTRIAL AND CIVIL ENGINEERING, PTS 1-4, 2012, 594-597 : 2251 - 2256
  • [40] Numerical investigation on the stack effect of a general high-rise building model
    Xie X.-F.