Second order sliding mode control of three-level four-leg DSTATCOM based on instantaneous symmetrical components theory

被引:13
作者
Bouafia S. [1 ]
Benaissa A. [1 ]
Barkat S. [2 ]
Bouzidi M. [1 ,3 ]
机构
[1] Intelligent Control and Electrical Power Systems Laboratory (ICEPS), Djillali Liabes University, Sidi-Bel-Abbès
[2] Department of Electrical Engineering, Electrical Engineering Laboratory, University of Mohamed Boudiaf, M’Sila
[3] Department of Electrical Engineering, University of Kasdi Merbah, Ouargla
关键词
Second order sliding mode controller; Three dimensional space vector modulation; Three-level four-leg DSTATCOM; Three-phase four-wire distribution system;
D O I
10.1007/s12667-016-0217-5
中图分类号
学科分类号
摘要
In this paper, a second order sliding mode controller (SOSMC) is proposed to control a three-level four-leg DSTATCOM connected to three-phase four-wire distribution system. The controller is designed in synchronous reference frame using super twisting algorithm based on symmetrical components theory. The proposed DSTATCOM control is aimed for the power factor correction in both capacitive and inductive operation modes. It has also purpose the regulation of excessive neutral current in the fourth wire of the distribution utility system under unbalanced loads or asymmetrical fault in the grid cases. This paper also presents a simplified three-level three-dimensional space vector modulation (3DSVM) with DC-bus capacitor voltages balancing strategy based on the effective use of the redundant switching states of the inverter voltage vectors. The effectiveness and validity of the proposed SOSMC system and 3DSVM are maintained by computer simulation. From simulation results, the comparison between the SOSMC, first order integral SMC, and conventional PI controller shows superiority of the SOSMC with high performance under both dynamic and steady state operations even in worst cases such as fault and unbalancing loads. © 2016, Springer-Verlag Berlin Heidelberg.
引用
收藏
页码:79 / 111
页数:32
相关论文
共 47 条
  • [1] Kersting W.H., Distribution system modeling and analysis. Power and Energy, Society, (2013)
  • [2] Singh B., Chandra A., Al-Haddad K., Kothari D.P., Reactive power compensation and load balancing in electric power distribution systems, Int. J. Electr. Power Energy Syst., 20, pp. 375-381, (1998)
  • [3] Bayliss C.R., Hardy, (2012)
  • [4] Sreenivasarao D., Agarwal P., Das B., Neutral current compensation in three-phase, four-wire systems: a review, Electr. Power Syst. Res., 86, pp. 170-180, (2012)
  • [5] Hingorani N.G., Gyugyi L., Understanding FACTS: concepts and technology of flexible AC transmission systems, (2000)
  • [6] Zhang X.-P., Rehtanz C., Pal B., Flexible AC Transmission Systems: Modelling and Control, Springer, (2012)
  • [7] Singh B., Al-Haddad K., Chandra A., Harmonic elimination, reactive power compensation and load balancing in three-phase, four-wire electric distribution systems supplying non-linear loads, Electr. Power Syst. Res., 44, pp. 93-100, (1998)
  • [8] Wu C.J., Chiang J.C., Yen S.S., Liao C.J., Yang J.S., Guo T.Y., Investigation and mitigation of harmonic amplification problems caused by single-tuned filters, IEEE Trans. Power Deliv., 13, pp. 800-806, (1998)
  • [9] Fukami T., Onchi T., Naoe N., Hanaoka R., Compensation for neutral current harmonics in a three-phase four-wire system by a synchronous machine, IEEE Trans. Ind. Appl., 38, pp. 1232-1236, (2002)
  • [10] Khera P.P., Application of zigzag transformers for reducing harmonics in the neutral conductor of low voltage distribution system, Conference Record of the 1990 IEEE Industry Applications Society Annual Meeting, pp. 1092-1096, (1990)