Robust Control of Three-Phase VSI with LCL Filter for Distributed Generation Power Quality Improvement

被引:0
作者
José Carlos Ugaz Peña
Leonardo Poltronieri Sampaio
Moacyr Aureliano Gomes de Brito
Carlos Alberto Canesin
机构
[1] São Paulo State University-UNESP,Power Electronics Laboratory
[2] Federal University of Technology-Paraná-UTFPR,Department of Electrical Engineering – DEL
[3] Federal University of Mato Grosso do Sul-UFMS,undefined
来源
Journal of Control, Automation and Electrical Systems | 2020年 / 31卷
关键词
Grid-connected inverter; LCL filter; Linear matrix inequalities (LMIs); Microgrid inverter; Robust control;
D O I
暂无
中图分类号
学科分类号
摘要
This paper proposes a methodology to control a three-phase voltage source inverter with LCL filter for distributed generation (DG) in microgrid scenario. Thus, the presented control strategy allows the DG system to operate in both grid-connected and islanded modes with a smooth transition between them. Therefore, the DG control system strategy is performed by splitting the control input into two control-stages; the first one is in charge of reproducing sinusoidal voltages at the filter capacitors; meanwhile, the second is dedicated to modulate these voltages in order to achieve proper amplitude and phase for correct output current injection. By means of discrete-time state-space representation of the system, state-feedback controllers are obtained employing linear matrix inequalities considering uncertainties on grid inductances and optimization of the H2 norm for each operation mode. Finally, the feasibility of the proposed DG system is demonstrated and validated through computational simulations, as well as experimental evaluations.
引用
收藏
页码:1051 / 1062
页数:11
相关论文
共 42 条
[1]  
Buduma P(2018)Robust nested loop control scheme for LCL-filtered inverter-based DG unit in grid-connected and islanded modes IET Renewable Power Generation 12 1269-1285
[2]  
Panda G(2013)Evaluation of the main MPPT techniques for photovoltaic applications IEEE Transactions on Industrial Electronics 60 1156-1167
[3]  
de Brito MAG(1999)A new discrete-time robust stability condition Systems & Control Letters 37 261-265
[4]  
Galotto L(2002)Extended H 2 and H norm characterizations and controller parametrizations for discrete-time systems International Journal of Control 75 666-679
[5]  
Sampaio LP(2011)Hierarchical control of droop-controlled AC and DC microgrids—A general approach toward standardization IEEE Transactions on Industrial Electronics 58 158-172
[6]  
de Azevedo Melo G(2015)Robust optimal current control for grid- connected three-phase pulse-width modulated converters IET Power Electronics 8 1490-1499
[7]  
Canesin CA(2014)LMI-based control for grid-connected converters with LCL filters under uncertain parameters IEEE Transactions on Power Electronics 29 3776-3785
[8]  
de Oliveira MC(2014)Trends in Microgrid Control IEEE Transactions on Smart Grid 5 1905-1919
[9]  
Bernussou J(2016)Grid-tie three-phase inverter with active power injection and reactive power compensation Renewable Energy 85 854-864
[10]  
Geromel JC(2003)Grid current regulation of a three-phase voltage source inverter with an LCL input filter IEEE Transactions on Power Electronics 18 888-895