Exploring heating performance of gas engine heat pump with heat recovery

被引:0
作者
Fu-jiang Dong
Feng-guo Liu
Xian-ting Li
Xue-yi You
Dong-fang Zhao
机构
[1] Tianjin Chengjian University,School of Energy and Safety Engineering
[2] Tsinghua University,School of Architecture
[3] Tianjin University,School of Environmental Science and Engineering
来源
Journal of Central South University | 2016年 / 23卷
关键词
gas engine heat pump; coefficient of performance; primary energy ratio; heating mode; heat recovery;
D O I
暂无
中图分类号
学科分类号
摘要
In order to evaluate the heating performance of gas engine heat pump (GEHP) for air-conditioning and hot water supply, a test facility was developed and experiments were performed over a wide range of engine speed (1400-2600 r/min), ambient air temperature (2.4-17.8 °C) and condenser water inlet temperature (30-50 °C). The results show that as engine speed increases from 1400 r/min to 2600 r/min, the total heating capacity and energy consumption increase by about 30% and 89%, respectively; while the heat pump coefficient of performance (COP) and system primary energy ratio (PER) decrease by 44% and 31%, respectively. With the increase of ambient air temperature from 2.4 °C to 17.8 °C, the heat pump COP and system PER increase by 32% and 19%, respectively. Moreover, the heat pump COP and system PER decrease by 27% and 15%, respectively, when the condenser water inlet temperature changes from 30 °C to 50 °C. So, it is obvious that the effect of engine speed on the performance is more significant than the effects of ambient air temperature and condenser water inlet temperature.
引用
收藏
页码:1931 / 1936
页数:5
相关论文
共 51 条
[11]  
Yang Zhao(2005)Experimental investigation of a micro-combined cooling, heating and power system driven by a gas engine [J]. International Journal of Refrigeration 28 977-987
[12]  
Sanaye S(2013)Dynamic modeling of gas engine driven heat pump system in cooling mode [J]. Energy 55 195-208
[13]  
Chahartaghi M(2009)Noise control of GEHP’s noise isolation device [J]. Journal of Vibration and Shock 28 192-198
[14]  
Elgendy E(2009)An experimental study of a direct expansion ground-coupled heat pump system in heating mode [J]. International Journal of Energy Research 33 1367-1383
[15]  
Schmidt J(2010)Comparison of natural gas driven heat pumps and electrically driven heat pumps with conventional systems for building heating purposes [J]. Energy and Buildings 42 904-908
[16]  
Khalil A(undefined)undefined undefined undefined undefined-undefined
[17]  
Fatouh M(undefined)undefined undefined undefined undefined-undefined
[18]  
Yang Z(undefined)undefined undefined undefined undefined-undefined
[19]  
Wang W-b(undefined)undefined undefined undefined undefined-undefined
[20]  
Wu Xi(undefined)undefined undefined undefined undefined-undefined