Exploring heating performance of gas engine heat pump with heat recovery

被引:0
作者
Fu-jiang Dong
Feng-guo Liu
Xian-ting Li
Xue-yi You
Dong-fang Zhao
机构
[1] Tianjin Chengjian University,School of Energy and Safety Engineering
[2] Tsinghua University,School of Architecture
[3] Tianjin University,School of Environmental Science and Engineering
来源
Journal of Central South University | 2016年 / 23卷
关键词
gas engine heat pump; coefficient of performance; primary energy ratio; heating mode; heat recovery;
D O I
暂无
中图分类号
学科分类号
摘要
In order to evaluate the heating performance of gas engine heat pump (GEHP) for air-conditioning and hot water supply, a test facility was developed and experiments were performed over a wide range of engine speed (1400-2600 r/min), ambient air temperature (2.4-17.8 °C) and condenser water inlet temperature (30-50 °C). The results show that as engine speed increases from 1400 r/min to 2600 r/min, the total heating capacity and energy consumption increase by about 30% and 89%, respectively; while the heat pump coefficient of performance (COP) and system primary energy ratio (PER) decrease by 44% and 31%, respectively. With the increase of ambient air temperature from 2.4 °C to 17.8 °C, the heat pump COP and system PER increase by 32% and 19%, respectively. Moreover, the heat pump COP and system PER decrease by 27% and 15%, respectively, when the condenser water inlet temperature changes from 30 °C to 50 °C. So, it is obvious that the effect of engine speed on the performance is more significant than the effects of ambient air temperature and condenser water inlet temperature.
引用
收藏
页码:1931 / 1936
页数:5
相关论文
共 51 条
[1]  
Zhang R R(2005)Analysis on the heating performance of a gas engine driven air to water heat pump based on a steady-state model [J]. Energy Conversion and Management 46 1714-1730
[2]  
Lu X S(1987)Introduction to engine-driven heat pumps— Concepts, approach, and economics [J]. ASHRAE Trans 93 987-996
[3]  
Li S Z(2007)Modeling and dynamic control simulation of unitary gas engine heat pump [J]. Energy Conversion and Management 48 3146-3153
[4]  
Lin W S(2009)Saving energy in the heat-pump air conditioning system driven by gas engine [J]. Energy and Buildings 41 206-211
[5]  
Gu A Z(2010)Thermal modeling and operating tests for the gas engine-driven heat pump systems [J]. Energy 35 351-363
[6]  
Colosimo D D(2011)Performance of a gas engine driven heat pump for hot water supply systems [J]. General Information 36 2883-2889
[7]  
Yang Z(2013)Thermal modeling and operating tests for a gas-engine driven heat pump working as a water heater in winter [J]. Energy and Buildings 58 219-226
[8]  
Zhao H-b(2013)Performance study of parallel-type hybrid-power gas engine-driven heat pump system [J]. Energy and Buildings 62 37-44
[9]  
Fang Zheng(2010)Experimental study of gas engine driven air to water heat pump in cooling mode [J]. General Information 35 2461-2467
[10]  
Xu Z-j(2010)Performance of a gas engine heat pump (GEHP) using R410A for heating and cooling applications [J]. Energy 35 4941-4948