Frequency-feedback based islanding detection algorithm for micro-grid

被引:0
作者
Li Y. [1 ]
Li S. [1 ]
Bai S. [1 ]
Niu C. [1 ]
机构
[1] Key Laboratory of Power System Simulation and Control, Tianjin University
关键词
Distributed generation; Islanding detection; Micro-grid; Reactive power compensation;
D O I
10.1007/s12209-008-0016-8
中图分类号
学科分类号
摘要
The unintentional islanding of micro-grid may cause negative impacts on distribution loads and distributed generations, so it must be detected within the acceptable duration. In this paper a new islanding detection algorithm is proposed. This algorithm introduces the frequency feedback method by the reactive power compensation to derive the frequency continuous shift. Accordingly, the islanding can be detected by monitoring the frequency within 0.1 s. The simulation results prove that this algorithm has extremely small non-detection zone, and meanwhile it presents an excellent islanding detection speed as well.
引用
收藏
页码:85 / 91
页数:6
相关论文
共 18 条
[1]  
Robert L., Integration of distributed energy resources - The CERTS micro-grid concept, (2002)
[2]  
Jeraputra C., Enjeti P., Development of a robust anti-islanding algorithm for utility interconnection of distributed fuel cell powered generation, Proceedings of the 19th Annual IEEE Applied Power Electronics Conference and Exposition-APEC 2004, pp. 1534-1540, (2004)
[3]  
John S., Russel B., Jerry G., Development and testing of an approach to anti-islanding in utility-interconnected photovoltaic systems, pp. 1932-1939, (2000)
[4]  
IEEE recommended practice for utility interface of photovoltaic (PV) systems
[5]  
Draft standard for interconnecting distributed resources with electric power systems
[6]  
Inverters, converters, and controllers for use in independent power systems
[7]  
Ropp M.E., Begovic M., Rohatgi A., Determining the relative effectiveness of islanding detection methods using phase criteria and non-detection zones, IEEE Transactions on Energy Conversion, 15, 3, pp. 290-296, (2000)
[8]  
Ward B., Michael R., Evaluation of islanding detection methods for photovoltaic utility-interactive power systems, (2002)
[9]  
Ye Z., Kolwalkar A., Zhang Y., Evaluation of anti-islanding schemes based on non-detection zone concept, IEEE Transactions on Power Electronics, 19, 5, pp. 1171-1176, (2004)
[10]  
Hung G.-K., Chang C.-C., Chen C.-L., Automatic phase-shift method for islanding detection of grid-connected photovoltaic inverters, IEEE Transactions on Energy Conversion, 18, 1, pp. 169-173, (2003)