Determination of the hydrogen diffusion coefficient in transformer oil

被引:0
作者
A. L. Bychkov
S. M. Korobeynikov
A. Yu. Ryzhkina
机构
[1] Novosibirsk State Technical University,
来源
Technical Physics | 2011年 / 56卷
关键词
Diffusion Coefficient; Diagnostic Data; Small Atom; Hydrogen Diffusion Coefficient; Dissolution Dynamic;
D O I
暂无
中图分类号
学科分类号
摘要
The hydrogen diffusion coefficient in transformer oil is determined by optically monitoring the dynamics of the hydrogen bubble dissolution in pure degassed oil. The diffusion coefficient is found to be roughly two orders of magnitude smaller than those determined earlier. This result is of great importance for chromatographic analysis of gases dissolved in transformer oil, since it gives grounds to suspect that hydrogen is not so volatile as implicitly believed in a number of works. Accordingly, the reliability of diagnostic data for high-voltage oil-filled equipment improves.
引用
收藏
页码:421 / 422
页数:1
相关论文
共 8 条
  • [1] Mikheev Gen. M.(2002)undefined Zh. Tekh. Fiz. 72 73-undefined
  • [2] Mikheev Georg. M.(2006)undefined Chem. Eng. Sci. 61 7697-undefined
  • [3] Fadeev E. G.(undefined)undefined undefined undefined undefined-undefined
  • [4] Popov A. Yu.(undefined)undefined undefined undefined undefined-undefined
  • [5] Kentisha S.(undefined)undefined undefined undefined undefined-undefined
  • [6] Lee J.(undefined)undefined undefined undefined undefined-undefined
  • [7] Davidson M.(undefined)undefined undefined undefined undefined-undefined
  • [8] Ashokkumar M.(undefined)undefined undefined undefined undefined-undefined