Pitting failure of copper pipings for emergency fire sprinkler in ground water

被引:0
|
作者
Seung-won Baek
Jong-kwon Lee
Jong-jip Kim
Kyung-ja Kim
机构
[1] Soonchunhyang University,Department of Materials Engineering
[2] KRISS Gajeongro 267,Department of Life Science
[3] Soonchunhyang University,undefined
来源
关键词
alloys; aging; corrosion; optical microscopy; failure analysis;
D O I
暂无
中图分类号
学科分类号
摘要
The possibility of microbiologically influenced corrosion was investigated in the early pitted copper pipes. The pipes were installed for less than 6 months as an immergency fire sprinkler. The bacteria were cultured by sampling of corrosion by-product near pits on failed copper pipes for the aerobic as well as anaerobic bacteria. However, only aerobic bacteria was found, which were Micrococcus Luteus and Bacillus sp.. The corrosion rate of copper pipes were studied by weight loss in the groundwater and polarization method. In immersion test as well as the electrochemical polarization test in ground water, only Micrococcus Luteus could activate corrosion of copper by 20% and 15%, respectively. On the other hand, Bacillus sp. showed little effect on corrosion in the above two tests. The shape and characteristics of failed copper pipes as well as simulated copper were investigated using stereoscope, optical microscopy, scanning electron microscope and EDS. The cause of pits were discussed, related with the dissolved copper concentrations, pH, and optical density. It could be concluded that the early failure of copper pipings could be ascribed to the acceration of copper in the presence of bacteria, i.e., Micrococcus Luteus.
引用
收藏
页码:479 / 484
页数:5
相关论文
共 50 条
  • [1] Pitting Failure of Copper Pipings for Emergency Fire Sprinkler in Ground Water
    Baek, Seung-won
    Lee, Jong-kwon
    Kim, Jong-jip
    Kim, Kyung-ja
    METALS AND MATERIALS INTERNATIONAL, 2015, 21 (03) : 479 - 484
  • [2] Analysis of pitting corrosion failure of copper tubes in an apartment fire sprinkler system
    Suh, Sang Hee
    Suh, Youngjoon
    Yoon, Hyung Goog
    Oh, Jeong Han
    Kim, Youngjun
    Jung, Kimin
    Kwon, HyukSang
    ENGINEERING FAILURE ANALYSIS, 2016, 64 : 111 - 125
  • [3] Pitting corrosion of copper tubes for fire sprinkler system
    Ko, Sang-Jin
    Lee, Yun-Ho
    Nam, Ki-Seok
    Park, Eun-Ha
    Kim, Jung-Gu
    ENGINEERING FAILURE ANALYSIS, 2022, 141
  • [4] Effect of oxygen on pitting corrosion of copper pipe in fire sprinkler system
    Lee, Yun-Ho
    Byun, Ji-Hae
    Ko, Sang-Jin
    Park, Eun-Ha
    Kim, Jung-Gu
    MATERIALS CHEMISTRY AND PHYSICS, 2023, 301
  • [5] Inhibition of Pitting Corrosion Failure of Copper Tubes in Wet Sprinkler Systems
    Suh, Sang Hee
    Suh, Youngjoon
    Lee, Jonghyuk
    Kwon, HyukSang
    CORROSION SCIENCE AND TECHNOLOGY-KOREA, 2020, 19 (02): : 89 - 99
  • [6] Fire Sprinkler Heads, Design, and Failure
    Garber, R. I.
    JOURNAL OF FAILURE ANALYSIS AND PREVENTION, 2009, 9 (06) : 495 - 498
  • [7] Analysis of copper pitting failure in drinking water distribution system
    Jia Z.
    Du C.
    Zhang D.
    Li X.
    Journal of Failure Analysis and Prevention, 2011, 11 (02) : 152 - 157
  • [8] Inhibition of Pitting Corrosion Failure of Copper Tubes in Wet Sprinkler Systems (vol 19, pg 89, 2020)
    Suh, Sang Hee
    Suh, Youngjoon
    Lee, Jonghyuk
    Kwon, HyukSang
    CORROSION SCIENCE AND TECHNOLOGY-KOREA, 2020, 19 (03): : 108 - 108
  • [9] Delivering water to multifamily fire sprinkler systems
    1600, Public Works Journal Corp, Ridgewood, NJ, United States (126):
  • [10] Evaporation of sprinkler water spray in a fire plume
    Krishan, G
    Prakash, S
    IECEC-97 - PROCEEDINGS OF THE THIRTY-SECOND INTERSOCIETY ENERGY CONVERSION ENGINEERING CONFERENCE, VOLS 1-4: VOL.1: AEROSPACE POWER SYSTEMS AND TECHNOL; VOL 2: ELECTROCHEMICAL TECHNOL, CONVERSION TECHNOL, THERMAL MANAGEMENT; VOLS 3: ENERGY SYSTEMS, RENEWABLE ENERGY RESOURCES, ENVIRONMENTAL IMPACT, POLICY IMPACTS ON ENERGY; VOL 4: POST DEADLINE PAPERS, INDEX, 1997, : 1433 - 1438