Cost Optimization of Heat Exchanger Inventory in Cascade Refrigeration Cycles

被引:0
作者
Bilal A. Qureshi
Syed M. Zubair
机构
[1] King Fahd University of Petroleum and Minerals,Mechanical Engineering Department
[2] IRC for Renewable Energy and Power Systems,undefined
[3] King Fahd University of Petroleum and Minerals,undefined
来源
Arabian Journal for Science and Engineering | 2023年 / 48卷
关键词
Thermoeconomics; Cascade; Non-dimensional cost; Overall conductance;
D O I
暂无
中图分类号
学科分类号
摘要
In this work, the cost optimal distribution of the overall conductance of all the heat exchangers is investigated from a thermoeconomic point-of-view in cascade refrigeration cycles using the endoreversible case. Non-dimensional cost functions are developed and investigated for a constant value of the rate of work, rate of cooling, rate of heat rejection and heat transfer rate for the cascade heat exchanger. These can be used to predict the minimum initial cost of the heat exchangers under the specified thermal conditions. All the cost functions showed an optimum point in relation to the absolute condenser temperature ratio (θ1) wherein the case of fixed heat rejection rate from the condenser gave the lowest cost values and the case of constant rate of work gave the highest cost values with it being 3 times higher at the optimum point. For the former case, a 1% increase in evaporator to condenser fluid temperature ratio (Φ) resulted in an average increase of 4.7% in the cost function value. For the case of fixed cooling rate, the corresponding cost function had an optimum value with respect to the non-dimensional temperature difference in the cascade heat exchanger. In this case, for a 5% increase in θ1, the cost value decreased by ~ 7%; although this decrease was larger for lower values of Φ. Also, investigation into the unit cost ratio of the system showed that the condenser contributed the most (42%-65%) to the total overall conductance.
引用
收藏
页码:12513 / 12522
页数:9
相关论文
共 65 条
  • [1] Llopis R(2015)Energy and environmental comparison of two-stage solutions for commercial refrigeration at low temperature: fluids and systems Appl. Energy 138 133-142
  • [2] Sánchez D(2021)Comparative energy and exergy analysis of a subcritical cascade refrigeration system using low global warming potential refrigerants Appl. Therm. Eng. 32 1631-1639
  • [3] Sanz-Kock C(1989)Theory of heat transfer-irreversible refrigeration plants Int. J. Heat Mass Transf. 115 148-150
  • [4] Cabello R(1993)Power and refrigeration plants for minimum heat exchanger inventory J. Energy Resour. Technol. 38 2997-3004
  • [5] Torrella E(1995)Optimal allocation of a heat-exchanger inventory in heat driven refrigerators Int. J. Heat Mass Transf. 77 339-354
  • [6] Aktemur C(2004)Optimal allocation of heat-exchanger area for refrigeration and air-conditioning plants Appl. Energy 15 181-185
  • [7] Ozturk IT(1992)Design considerations for refrigeration cycles Int. J. Refrig. 36 7-10
  • [8] Cimsit C(1995)Maximum obtainable specific cooling load of a refrigerator Energy Convers. Manag. 20 1049-1053
  • [9] Bejan A(1995)Optimization of the specific rate of refrigeration in combined refrigeration cycles Energy 20 1285-1289
  • [10] Bejan A(1995)Steady-state thermodynamic analysis of a combined carnot cycle with internal irreversibility Energy 39 579-588