AGC of restructured multi-area multi-source hydrothermal power systems incorporating energy storage units via optimal fractional-order fuzzy PID controller

被引:0
作者
Yogendra Arya
机构
[1] Maharaja Surajmal Institute of Technology,Department of Electrical and Electronics Engineering
来源
Neural Computing and Applications | 2019年 / 31卷
关键词
Multi-area multi-source system; Fractional-order PID controller; Fuzzy PID controller; Automatic generation control; Restructured power system;
D O I
暂无
中图分类号
学科分类号
摘要
Owing to nonlinear structure and uncertain load demand characteristics, expert and intelligent automatic generation control (AGC) is inevitable for coherent operation and control of electric power system. Hence, in this paper, to mitigate the frequency and power deviations efficiently under sudden load demand conditions, a novel fractional-order fuzzy PID (FOFPID) controller is suggested in AGC of restructured multi-area multi-source hydrothermal power systems. The parameters of FOFPID controller are optimized by utilizing bacterial foraging optimization algorithm. The controller is implemented on restructured two- and three-area systems. It is observed that the advocated method shows superiority over fuzzy PID, fractional-order PID and conventional PID control schemes. Energy storage units such as redox flow batteries (RFB) which show extremely long charge–discharge life cycle and outstanding quick response to alleviate the system oscillations under disturbances have further been incorporated into the studied systems to analyze their efficacy in boosting AGC performance. Analysis of results reveals that with RFB, system transient performance improves significantly. It is also observed that the obtained results satiate the AGC requirement under different power transactions taking place in a deregulated market in the presence/absence of appropriate generation rate constraint treated for thermal and hydro plants. Finally, the robustness of the presented approach is demonstrated against the wide variations in the system parameters and initial loading condition.
引用
收藏
页码:851 / 872
页数:21
相关论文
共 121 条
  • [11] Kumar N(2016)Design and analysis of BFOA-optimized fuzzy PI/PID controller for AGC of multi-area traditional/restructured electrical power systems Soft Comput 64 9-23
  • [12] Gorripotu TS(2015)A hybrid firefly algorithm and pattern search technique for automatic generation control of multi area power systems Int J Elect Power Energy Syst 73 632-643
  • [13] Sahu RK(2015)Cuckoo search algorithm based load frequency controller design for nonlinear interconnected power system Int J Electr Power Energy Syst 77 166-177
  • [14] Panda S(2016)Load frequency controller design via BAT algorithm for nonlinear interconnected power system Int J Electr Power Energy Syst 7 429-442
  • [15] Arya Y(2016)Load frequency controller design of a two-area system composing of PV grid and thermal generator via firefly algorithm Neural Comput Appl 64 56-66
  • [16] Arya Y(2016)Application of flower pollination algorithm in load frequency control of multi-area interconnected power system with nonlinearity Neural Comput Appl 15 23-34
  • [17] Kumar N(2015)BFOA based FOPID controller for multi area AGC system with capacitive energy storage Int J Electr Eng Inf 20 1-17
  • [18] Nanda J(2016)Design of a fractional order PID controller using GBMO algorithm for load-frequency control with governor saturation consideration ISA Trans 7 2175-2186
  • [19] Mishra S(2015)Solution approach to automatic generation control problem using hybridized gravitational search algorithm optimized PID and FOPID controllers Adv Electr Comput Eng 62 19-29
  • [20] Saikia LC(2017)Applying fractional order PID to design TCSC-based damping controller in coordination with automatic generation control of interconnected multi-source power system Eng Sci Technol Int J 42 2641-2649