Fault location method for partial coupling four-circuit overhead lines with different voltages

被引:0
作者
Ahmed Saber
机构
[1] Cairo University,Department of Electrical Power Engineering
来源
Electrical Engineering | 2020年 / 102卷
关键词
Transmission line theory; Fault location; Partial coupling four-circuit overhead line; Phasor measurement unit;
D O I
暂无
中图分类号
学科分类号
摘要
Few research articles discussed the issue of fault location for partial coupling four-circuit overhead lines with different voltages. In this work, a fault location method is proposed for partial coupling untransposed four-circuit overhead line with different voltages on the same tower using synchronized current data. The distributed-parameter model of the line and the mutual couplings between all circuits are considered. The faulty circuits are initially recognized, and the deduced analytical equation for fault location does not depend on fault type or fault resistance. In addition, the locations of normal-shunt faults, cross-circuit faults and cross-voltage faults between different voltage levels are estimated precisely. Emulation studies are conducted by DIgSILENT Power Factory and MATLAB software to validate the proposed method under various fault resistances, fault locations and fault inception angles. In addition, the effect of estimation errors in line parameters as well as measurement and synchronization errors is tested.
引用
收藏
页码:529 / 538
页数:9
相关论文
共 25 条
[1]  
Ismail HM(2002)Magnetic field of high-phase order and compact transmission lines Int J Energy Res 26 45-55
[2]  
Fan C(2011)A fault-location method for 12-phase transmission lines based on twelve-sequence-component IEEE Trans Power Deliv 26 135-142
[3]  
Liu ML(2012)One-end fault location method for untransposed four-circuit transmission lines Int J Electr Power Energy Syst 43 660-669
[4]  
Tian Y(2017)An accurate fault location method for multi-circuit series compensated transmission lines IEEE Trans Power Syst 32 572-580
[5]  
Ngu EE(2018)New fault location scheme for four-circuit untransposed transmission lines Int J Electr Power Energy Syst 99 225-232
[6]  
Ramar K(2019)A new fault location technique for four-circuit series-compensated transmission lines Int Trans Electr Energy Syst 29 1-15
[7]  
Eissa A(2017)Distance protection of multiple-circuit shared tower transmission lines with different voltages—part I: fault current magnitude IET Gener Transm Distrib 11 2618-2625
[8]  
Gajare A(2017)Distance protection of multiple-circuit shared tower transmission lines with different voltages—part II: fault loop impedance IET Gener Transm Distrib 11 2626-2632
[9]  
Pradhan AK(2018)A new fault location method for partial coupling double-circuit untransposed transmission line with shared tower and different voltages Electr Power Comp Syst 46 1210-1221
[10]  
Saber A(2018)A new fault location algorithm for multi-terminal mixed lines with shared tower and different voltage levels IET Gener Transm Distrib 12 2029-2037