Effects of Electronic Loads on Electrical Measurements, Power Quality and Billing

被引:6
作者
da Silva R.P.B. [1 ,2 ]
Quadros R. [1 ]
Santilio F.P. [1 ]
da Silva L.C.P. [2 ]
Carvalho B.C. [1 ]
de Vasconcellos A.B. [1 ]
机构
[1] Department of Electrical Engineering, Federal University of Mato Grosso (UFMT), Cuiabá
[2] School of Electrical and Computer Engineering, University of Campinas (UNICAMP), Campinas
关键词
Dimmer Flex; Harmonic distortion; Power factor; Switched loads;
D O I
10.1007/s40313-017-0330-2
中图分类号
学科分类号
摘要
This paper presents results from experimental studies carried out using an electronic device called a Dimmer Flex, developed at the Federal University of Mato Grosso, Brazil. The Dimmer Flex is able to evaluate the effects of electronically switched loads regarding electrical measurements, especially focusing on billing. It can be concluded from the studies that, depending on the switching characteristics, a switched load can be “transformed” to the meter in a load with inductive or capacitive behavior, therefore “absorbing or injecting” reactive power to the system it is connected to. This finding shows that electronically switched loads can interfere in electrical measurements and consequently may affect the billing process, underlining the need to evaluate, discuss and even review current measurement and billing methods. © 2017, Brazilian Society for Automatics--SBA.
引用
收藏
页码:654 / 663
页数:9
相关论文
共 23 条
  • [1] Technical Note No. 0083/2012 – SRD/ANEEL. Brazilian Electricity Regulatory Agency, (2012)
  • [2] Brasília, (2010)
  • [3] Belchior F.N., Galvao T.M., Ribeiro P.F., Silveira P.M., Comparative analysis of power quality instruments in measuring power under distorted conditions. International Journal of Emerging Electric Power Systems, 16(5), 421–429. ISSN (Online) 1553-779X, ISSN (Print) 2194-5756, 2015, (2015)
  • [4] Beltran-Carbajal F., Silva-Navarro G., A fast parametric estimation approach of signals with multiple frequency harmonics, Electric Power Systems Research, 144, pp. 157-162, (2017)
  • [5] Cataliotti A., Cosentino V., Lipari A., Nuccio S., Metrological characterization and operating principle identification of static meters for reactive energy: an experimental approach under nonsinusoidal test conditions, IEEE Transactions on Instrumentation and Measurement, 58, 5, pp. 1427-1435, (2009)
  • [6] do Alves H.N., Power factor correction and harmonic filtering planning in electrical distribution network, Journal of Control, Automation and Electrical Systems, 4, pp. 1-11, (2016)
  • [7] Fernandez F.M., Nair P.S.C., A new expression for power factor under nonsinusoidal conditions, Innovative Smart Grid Technologies - India (ISGT India) 2011 IEEE PES, pp. 155-159, (2011)
  • [8] Ferreira D.D., Nagata E.A., Ferreira S.C., de Seixas J.M., Duque C.A., Marques C.A.G., Guedes J.D.S., Cerqueira A.S., Method based on independent component analysis for harmonic extraction from power system signals, Electric Power Systems Research, 119, pp. 19-24, (2015)
  • [9] Fiorucci E., The measurement of actual apparent power and actual reactive power from the instantaneous power signals in single-phase and three-phase systems, Electric Power Systems Research, 121, pp. 227-242, (2015)
  • [10] Hansen S., Nielsen P., Blaabjerg F., Harmonic cancellation by mixing nonlinear single-phase and three-phase loads, IEEE Transactions on Industry Applications, 36, 1, pp. 152-159, (2000)