The monitoring results of electromagnetic radiation of 110-kV high-voltage lines in one urban location in Chongqing P.R. China

被引:0
|
作者
Qi-zhong Qin
Yu Chen
Ting-ting Fu
Li Ding
Ling-li Han
Jian-chao Li
机构
[1] Chongqing Medical University,Department of Labor Sanitation and Environment, the School of Public Health
来源
关键词
110-kV high-voltage lines; Electromagnetic radiation; Electric fields; Magnetic fields; Monitoring results;
D O I
暂无
中图分类号
学科分类号
摘要
To understand electromagnetic radiation field strength and its influencing factors of certain 110-kV high-voltage lines in one urban area of Chongqing by measuring 110-kV high-voltage line’s electromagnetic radiation level. According to the methodology as determined by the National Hygienic Standards, we selected certain adjacent residential buildings, high-voltage lines along a specific street and selected different distances around its vertical projection point as monitoring points. The levels of electromagnetic radiations were measured respectively. In this investigation within the frequency of 5–1,000 Hz both the electric field strength and magnetic field strength of each monitoring sites were lower than the public exposure standards as determined by the International Commission on Non-Ionizing Radiation Protection. However, the electrical field strength on the roof adjacent to the high-voltage lines was significantly higher than that as measured on the other floors in the same buildings (p < 0.05). The electromagnetic radiation measurements of different monitoring points, under the same high-voltage lines, showed the location which is nearer the high-voltage line maintain a consistently higher level of radiation than the more distant locations (p < 0.05). Electromagnetic radiation generated by high-voltage lines decreases proportionally to the distance from the lines. The buildings can to some extent shield (or absorb) the electric fields generated by high-voltage lines nearby. The electromagnetic radiation intensity near high-voltage lines may be mitigated or intensified by the manner in which the high-voltage lines are set up, and it merits attention for the potential impact on human health.
引用
收藏
页码:1533 / 1540
页数:7
相关论文
共 4 条
  • [1] The monitoring results of electromagnetic radiation of 110-kV high-voltage lines in one urban location in Chongqing PR China
    Qin, Qi-zhong
    Chen, Yu
    Fu, Ting-ting
    Ding, Li
    Han, Ling-li
    Li, Jian-chao
    ENVIRONMENTAL MONITORING AND ASSESSMENT, 2012, 184 (03) : 1533 - 1540
  • [2] Measurement and Analysis of Electromagnetic Radiation of 110KV High-voltage Lines in one Urban Location in Chongqing P. R. China
    Qin Qi-zhong
    Chen Yu
    Fu Ting-ting
    Ding Li
    Li Jian-chao
    Han Ling-li
    2010 4TH INTERNATIONAL CONFERENCE ON BIOINFORMATICS AND BIOMEDICAL ENGINEERING (ICBBE 2010), 2010,
  • [3] Resonant Wireless Charging System Design for 110-kV High-Voltage Transmission Line Monitoring Equipment
    Cai, Changsong
    Wang, Junhua
    Liu, Rong
    Fang, Zhijian
    Zhang, Pengcheng
    Long, Mengjiao
    Hu, Meilin
    Lin, Zhongzheng
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2019, 66 (05) : 4118 - 4129
  • [4] A comparison of magnetic fields inside and outside high-voltage urban 110-kV power substations with the exposure recommendations of the Ukrainian regulatory authorities
    Okun, Oleksandr
    Shevchenko, Sergey
    Korpinen, Leena
    RADIATION PROTECTION DOSIMETRY, 2013, 154 (04) : 417 - 429