Experimental and numerical investigation on a new type of heat exchanger in ground source heat pump system

被引:0
作者
Xichen Liu
Yimin Xiao
Kiao Inthavong
Jiyuan Tu
机构
[1] Chongqing University,College of Urban Construction and Environmental Engineering
[2] RMIT University,School of Aerospace, Mechanical and Manufacturing Engineering
来源
Energy Efficiency | 2015年 / 8卷
关键词
Renewable energy; Ground source heat pump; 3I-type heat exchanger; Experimental test; CFD;
D O I
暂无
中图分类号
学科分类号
摘要
Based on deficiencies of existing underground heat exchangers, a new design is proposed which consists of one outlet and three inlet pipes. Experimental measurements to evaluate the performance of single-U, double-U, and the new design referred to as 3I, for three inlet pipes, were carried out which showed superior performance of the 3I design. Experimental results showed that when under a constant heating load, the average circulating water temperature (ACWT) of the 3I-type was 3.7 and 1 °C lower than that of single-U and double-U, respectively. The thermal resistance of the 3I-type was 15.8 and 31.1 % lower than that of double-U and single-U type. In addition, numerical simulations were performed to further investigate the heat transfer performance over a very long operating time. Numerical results showed that for long-term operation under constant heating load, the ACWT of the 3I-type was 6.6 and 5.8 % lower than that of double-U type. Under a constant inlet water temperature that mimics a condenser output, the heat exchange per unit borehole depth of 3I-type was 17.1 and 11.6 % higher than that of double-U type in different operation conditions.
引用
收藏
页码:845 / 857
页数:12
相关论文
共 94 条
  • [1] Allan ML(2000)Materials characterization of superplasticized cement–sand grout Cement and Concrete Research 30 937-942
  • [2] Blumsack S(2012)Evaluation of federal and state subsidies for ground-source heat pumps Energy Efficiency 5 321-334
  • [3] Kleit A(2012)Domestic heat pumps in the UK: user behaviour, satisfaction and performance Energy Efficiency 5 283-301
  • [4] Smith SW(2011)Numerical simulation of vertical ground heat exchangers: intermittent operation in unsaturated soil conditions Computers and Geotechnics 38 949-958
  • [5] Caird S(2012)CFD simulations of horizontal ground heat exchangers: a comparison among different configurations Applied Thermal Engineering 33–34 24-32
  • [6] Roy R(2004)Heat transfer in ground heat exchangers with groundwater advection International Journal of Thermal Sciences 43 1203-1211
  • [7] Potter S(2012)An analysis of heat flow through a borehole heat exchanger validated model Applied Energy 92 523-533
  • [8] Choi JC(2013)Single and double U-tube ground heat exchangers in multiple-layer substrates Applied Energy 102 364-373
  • [9] Lee SR(2008)Thermal performance and ground temperature of vertical pile-foundation heat exchangers: a case study Applied Thermal Engineering 28 2295-2304
  • [10] Lee DS(2010)Experiment and simulation of temperature characteristics of intermittently-controlled ground heat exchanges Renewable Energy 35 1169-1174