Condensation heat transfer and pressure drop of R-134a saturated vapour inside a brazed compact plate fin heat exchanger with serrated fin

被引:0
作者
K. V. Ramana Murthy
C. Ranganayakulu
T. P. Ashok Babu
机构
[1] Aeronautical Development Agency,Mechanical Engineering Department
[2] National Institute of Technology Karnataka (NITK),undefined
来源
Heat and Mass Transfer | 2017年 / 53卷
关键词
Heat Transfer Coefficient; Heat Exchanger; Vapour Quality; Condensation Heat Transfer; Plate Heat Exchanger;
D O I
暂无
中图分类号
学科分类号
摘要
This paper presents the experimental heat transfer coefficient and pressure drop measured during R-134a saturated vapour condensation inside a small brazed compact plate fin heat exchanger with serrated fin surface. The effects of saturation temperature (pressure), refrigerant mass flux, refrigerant heat flux, effect of fin surface characteristics and fluid properties are investigated. The average condensation heat transfer coefficients and frictional pressure drops were determined experimentally for refrigerant R-134a at five different saturated temperatures (34, 38, 40, 42 and 44 °C). A transition point between gravity controlled and forced convection condensation has been found for a refrigerant mass flux around 22 kg/m2s. In the forced convection condensation region, the heat transfer coefficients show a three times increase and 1.5 times increase in frictional pressure drop for a doubling of the refrigerant mass flux. The heat transfer coefficients show weak sensitivity to saturation temperature (Pressure) and great sensitivity to refrigerant mass flux and fluid properties. The frictional pressure drop shows a linear dependence on the kinetic energy per unit volume of the refrigerant flow. Correlations are provided for the measured heat transfer coefficients and frictional pressure drops.
引用
收藏
页码:331 / 341
页数:10
相关论文
共 51 条
  • [1] Yan Y-Y(1999)Condensation heat transfer and pressure drop of refrigerant R-134a in a plate heat exchanger Int J Heat Mass Transf 42 993-1006
  • [2] Lio H-C(2000)Condensation of R134a flowing inside helicoidal pipe Int J Heat Mass Transf 43 2553-2564
  • [3] Lin T-F(2005)Condensation heat transfer and pressure drop characteristics of R-134a in an annular helical pipe Int Commun Heat Mass Transf 32 1307-1316
  • [4] Kang HJ(2004)Experimental heat transfer coefficients during refrigerant vaporisation and condensation inside herringbone-type plate heat exchangers with enhanced surfaces Int J Heat Mass Transf 47 4125-4136
  • [5] Lin CX(2004)Condensation heat transfer and pressure drop of the brazed plate heat exchangers using R-134a J Enhanc Heat Transf 11 161-182
  • [6] Ebadian MA(1999)Pressure drop analysis of steam condensation in a plate heat exchanger Heat Transf Eng 20 71-77
  • [7] Han JT(2007)Refrigerant R134a vaporisation heat transfer and pressure drop inside a small brazed plate heat exchanger Int J Refrig 30 821-830
  • [8] Lin CX(2008)Refrigerant R134a condensation heat transfer and pressure drop inside a small brazed plate heat exchanger Int J Refrig 31 780-789
  • [9] Ebadian MA(2009)R410A condensation inside a commercial brazed plate heat exchanger Exp Thermal Fluid Sci 33 284-291
  • [10] Longo GA(2010)Heat transfer and pressure drop during hydrocarbon refrigerant condensation inside a brazed plate heat exchanger Int J Refrig 33 944-953