Improved Hausdorff Distance Based Pilot Protection for Multi-terminal HVDC system

被引:0
作者
Qing Huai
Liang Qin
Kaipei Liu
Yi Xu
Fangzhou Wang
Hua Ding
机构
[1] Wuhan University,School of Electrical Engineering and Automation
[2] State Grid Energy Conservation Service Co.,undefined
[3] Ltd,undefined
来源
Journal of Electrical Engineering & Technology | 2021年 / 16卷
关键词
Pilot protection; HVDC; Similarity; Hausdorff distance;
D O I
暂无
中图分类号
学科分类号
摘要
In order to overcome the weakness of dc line protection under high impedance fault, a traveling wave similarity based pilot protection method is proposed using improved Hausdorff Distance algorithm. The issue of asynchronous data, noise and anomalies are solved with the improved Hausdorff Distance algorithm. The instantaneous frequency based wave head detection method is used to overcome the problem of delay in protection start-up. Based on this protection scheme, external fault can be distinguished from internal faults regardless of fault impedance, fault location and fault type. Moreover, the faulty pole and fault direction are recognized via ratio of transient energy at line terminals. Taking the Zhangbei high voltage dc transmission project as an example, a four-terminal ring type dc grid model is developed in PSCAD/EMTDC platform for fault simulation and the data processing is performed in MATLAB platform. Based on the theoretical analysis and simulation study, the proposed pilot protection is verified with excellent fault impedance withstanding ability and robustness against noise, abnormal data and asynchronous data.
引用
收藏
页码:1955 / 1969
页数:14
相关论文
共 80 条
  • [1] Flourentzou N(2009)VSC-based HVDC power transmission systems: An overview IEEE Trans Power Electron 24 592-602
  • [2] Agelidis VG(2010)Multi-terminal VSC HVDC for the European supergrid: Obstacles Renew Sustain Energy Rev 14 3156-3163
  • [3] Demetriades GD(2018)A protection scheme for multi-terminal VSC-HVDC transmission systems IEEE Access 6 3159-3166
  • [4] Hertem DV(2003)Research on travelling wave protection criterion on HVDC transmission line Relay 31 41-44
  • [5] Ghandhari M(2012)Survey of relay protection technology for HVDC transmission lines Autom Electr Power Syst 36 123-129
  • [6] Raza A(2015)A novel fault detection method for VSC-HVDC transmission system of offshore wind farm Int J Electr Power Energy Syst 73 475-483
  • [7] Akhtar A(2014)A fault-location method for VSC-HVDC transmission lines based on natural frequency of current Int J Electr Power Energy Syst 63 347-352
  • [8] Jamil M(2017)A fault identification method for two-level VSC-HVDC DC line based on Pearson correlation of transient current Trans China Electr Soc 32 74-85
  • [9] Ai L(2019)Backup-protection scheme for multi-terminal HVDC system based on wavelet-packet-energy entropy IEEE Access 7 49790-49803
  • [10] Chen WH(2020)protection scheme for multiterminal HVDC system based on wavelet transform modulus maxima IEEJ Trans Elect Electron Eng 15 1147-1159