On the Coordination of Current Transformers and Relay Protection and Automation Operation of Electric-Power Systems in Transient Short-Circuit States

被引:5
作者
Kuzhekov S.L. [1 ]
Degtyarev A.A. [1 ]
机构
[1] NPF Kvazar, Novocherkassk
关键词
current transformer; error; relay protection; saturated state interval; transient state;
D O I
10.3103/S1068371217120094
中图分类号
学科分类号
摘要
Due to the increasing number of incorrect actions of relay protection in transient processes accompanied by saturation of current-transformer (CT) cores, there is a need for developing a domestic standard for protective CTs designed to operate in transient states. The following ways to provide proper relay protection operation in transient states accompanied by saturation of CTs in operation are considered: (a) CT shedding that includes an increase in control cables’ cross sections, (b) development of relay-protection and automation algorithms based on the recognition of crash conditions in an appropriate CT transformation time interval of 2–3 ms, (c) development of relay-protection and automation algorithms with virtual CT error compensation, and (d) development and introduction of new primary-current converters. It is concluded that, for existing large power plants with installed TPX current transformers, it is advisable to use improved digital relay-protection algorithms for information processing obtained from CTs, for example, by methods (b) and/or (c). © 2017, Allerton Press, Inc.
引用
收藏
页码:832 / 838
页数:6
相关论文
共 9 条
[1]  
Alekseev V.G., Nonperiodic components of short-circuit currents in superhigh voltage networks, (1987)
[2]  
Stognii B.S., Teoriya vysokovol’tnykh izmeritel’nykh preobrazovatelei peremennogo toka i napryazheniya (The Theory of High Voltage Measuring Transducers of AC Current and Voltage), (1984)
[3]  
Kuzhekov S.L., Ivankov Y.I., Kolesnikova L.D., Altynpara L.Z., Universal characteristics of voltage transformers in transient mode of short circuit, (1975)
[4]  
Ziegler G., Numerical Differential Protection. Principles and Applications, (2005)
[5]  
Kuzhekov S.L., Nudel'man G.S., The way to support proper operation of microprocessor devices of differential protection under current transformers saturation, (2009)
[6]  
Drozdov A.D., Kuzhekov S.L., The way to research shape of secondary current in protective current transformers under transient and steady-state conditions, (1971)
[7]  
Vanin V.K., Ambrosovskaya, (2015)
[8]  
Kazanskii V.E., Transformatory toka v ustroistvakh releinoi zashchity i avtomatiki (Current Transformers in Relay Protection and Automation Devices), (1978)
[9]  
Gurevich V., Optical current transformers: we need to be realists, (2010)