Experimental study and analytical modeling of thermosyphon loop for cooling data center racks

被引:0
作者
Chayan Nadjahi
Hasna Louahlia-Gualous
Stéphane Le Masson
机构
[1] Normandie University,Orange Labs
[2] Unicaen,undefined
[3] R&D,undefined
来源
Heat and Mass Transfer | 2020年 / 56卷
关键词
D O I
暂无
中图分类号
学科分类号
摘要
This paper presents experimental study and analytical model for a passive two-phase thermosyphon loop designed to remove directly the hot air flow inside a data center. The cooling loop with separated lines working without electricity is tested under different conditions. A mini-channel parallel-flow evaporator and a finned-tubes condenser are used to transfer heat from the data center to outside environment. Experimental tests are conducted with different n-pentane fill ratios. According to these tests, the cooling performance is showed and the refrigerant distribution is specified. The proposed steady-state model is based on the combination of the thermal and hydraulic models of the two-phase flow inside the loop. It well predicts the experimental results such as the mass flow rate and working fluid pressure drops. As investigated by the model, the most parameters influencing the cooling capacity are: the working fluid, the condenser tubes number and the outside temperature.
引用
收藏
页码:121 / 142
页数:21
相关论文
共 67 条
[1]  
Habibi Khalaj A(2017)A Review on efficient thermal management of air- and liquid-cooled data centers: From chip to the cooling system Appl Energy 205 1165-1188
[2]  
Halgamuge SK(2016)Experimental investigations of thermal managements solutions in data centers buildings for different arrangements of cold aisles containments J Build Eng 5 41-49
[3]  
Nada SA(2017)A review of current status of free cooling in datacenters Appl Therm Eng 114 1224-1239
[4]  
Elfeky KE(2012)The applied effect analysis of heat exchanger installed in a typical communication base station in Beijing of China Energy Procedia 14 620-625
[5]  
Daraghmeh HM(2015)Cooling Systems in Data Centers: State of Art and Emerging Technologies Energy Procedia 83 484-493
[6]  
Wang CC(2005)Pressure drop in riser and evaporator in an advanced two-phase thermosyphon loop Int J Refrig 28 725-734
[7]  
Bao L(2014)Two-phase loop thermosyphon using carbon dioxide applied to the cold end of a Stirling cooler Appl Therm Eng 73 549-558
[8]  
Wang J(2013)Two-phase thermosyphon loop for cooling outdoor telecommunication equipments Appl Therm Eng 50 1351-1360
[9]  
Kang L(2016)Experimental study on the thermal characteristics of micro channel separate heat pipe respect to different filling ratio Appl Therm Eng 102 375-382
[10]  
Capozzoli A(2017)Experimental and numerical investigation on a CO2 loop thermosyphon for free cooling of data centers Appl Therm Eng 111 1083-1090