An evaluation index for the control effect of the local ventilation systems on indoor air quality in industrial buildings

被引:0
作者
Yi Wang
Yingxue Cao
Bo Liu
Jiaping Liu
Yang Yang
Qun Yu
机构
[1] Xi’an University of Architecture and Technology,School of Environmental and Municipal Engineering
[2] Shaanxi Architectural Design and Research Institute,undefined
来源
Building Simulation | 2016年 / 9卷
关键词
evaluation index; local ventilation system; computational fluid dynamics (CFD); indoor air quality (IAQ); contaminant concentration distribution;
D O I
暂无
中图分类号
学科分类号
摘要
To evaluate the control effect on indoor air quality (IAQ) of the local ventilation systems in industrial buildings with centralized contaminant sources, a new index, namely, normalized concentration in the target zone (NC-TZ), was proposed in this paper. According to theoretical analysis, NC-TZ is non-dimensional and ranges from 0 to 1. When NC-TZ tends toward 0, the control effect of the local ventilation system on IAQ is more satisfactory. When NC-TZ tends toward 1, the control effect on IAQ is less satisfactory. The numerical simulation on a push–pull ventilation system with varying exhaust flow rates and varying distances between push and pull hoods was performed. The results demonstrate that for the same capture efficiency, changing the local ventilation system characteristics can change the control effect on the local environment. The results for obstacles at different positions also indicate that NC-TZ can clearly reflect the control effect on IAQ of the local ventilation systems in industrial buildings.
引用
收藏
页码:669 / 676
页数:7
相关论文
共 48 条
[1]  
Brown M(2006)Making sense of modernity’s maladies: Health and disease in the industrial revolution Endeavour 30 108-112
[2]  
Cao G(2014)Modelling and experimental study of performance of the protected occupied zone ventilation Energy and Buildings 68 515-531
[3]  
Sirén K(2015)Fast prediction of indoor pollutant dispersion based on reduced-order ventilation models Building Simulation 8 415-420
[4]  
Kilpeläinen S(1995)Comparison of different Numerical Heat Transfer, Part B: Fundamentals 28 353-369
[5]  
Cao S-J(2001) models for indoor air flow computations Chemico-Biological Interactions 135–136 535-553
[6]  
Meyers J(2011)A cohort mortality study among workers at a 1,3 butadiene facility Safety and Health at Work 2 26-33
[7]  
Chen Q(1983)Lymphohematopoietic cancer mortality and morbidity of workers in a refinery/petrochemical complex in Korea American Industrial Hygiene Association Journal 44 752-755
[8]  
Divine BJ(2013)Capture efficiency of local exhaust ventilation systems Journal of Wind Engineering and Industrial Aerodynamics 115 9-21
[9]  
Hartman CM(2011)Comparison of various types of Indoor Air 21 442-453
[10]  
Koh D-H(1994) models for pollutant emissions around a two-building configuration Building and Environment 29 319-323