Equivalent thermal resistance minimization for a circular disc heat sink with reverting microchannels based on constructal theory and entransy theory

被引:0
作者
Liang Wang
ZhiHui Xie
LinGen Chen
Rong Wang
HuiJun Feng
机构
[1] Naval University of Engineering,College of Power Engineering
[2] Wuhan Institute of Technology,Institute of Thermal Science and Power Engineering
[3] Wuhan Institute of Technology,School of Mechanical & Electrical Engineering
来源
Science China Technological Sciences | 2021年 / 64卷
关键词
constructal theory; entransy dissipation extremum principle; microchannel heat sink; electronics cooling; generalized thermodynamic optimization;
D O I
暂无
中图分类号
学科分类号
摘要
Thermal designs for microchannel heat sinks with laminar flow are conducted numerically by combining constructal theory and entransy theory. Three types of 3-D circular disc heat sink models, i.e. without collection microchannels, with center collection microchannels, and with edge collection microchannels, are established respectively. Compared with the entransy equivalent thermal resistances of circular disc heat sink without collection microchannels and circular disc heat sink with edge collection microchannels, that of circular disc heat sink with center collection microchannels is the minimum, so the overall heat transfer performance of circular disc heat sink with center collection microchannels has obvious advantages. Furthermore, the effects of microchannel branch number on maximum thermal resistance and entransy equivalent thermal resistance of circular disc heat sink with center collection microchannels are investigated under different mass flow rates and heat fluxes. With the mass flow rate increasing, both the maximum thermal resistances and the entransy equivalent thermal resistances of heat sinks with respective fixed microchannel branch number all gradually decrease. With the heat flux increasing, the maximum thermal resistances and the entransy equivalent thermal resistances of heat sinks with respective fixed microchannel branch number remain almost unchanged. With the same mass flow rate and heat flux, the larger the microchannel branch number, the smaller the maximum thermal resistance. While the optimal microchannel branch number corresponding to minimum entransy equivalent thermal resistance is 6.
引用
收藏
页码:111 / 121
页数:10
相关论文
共 197 条
[1]  
Sohel Murshed S M(2017)A critical review of traditional and emerging techniques and fluids for electronics cooling Renew Sustain Energy Rev 78 821-833
[2]  
Nieto de Castro C A(1998)A novel concept for convective heat transfer enhancement Int J Heat Mass Transfer 41 2221-2225
[3]  
Guo Z Y(2019)A comprehensive review and comparison on heatline concept and field synergy principle Int J Heat Mass Transfer 135 436-459
[4]  
Li D Y(2014)Convective heat transfer enhancement: Mechanisms, techniques, and performance evaluation Adv Heat Transfer 46 87-186
[5]  
Wang B X(2009)Physical quantity synergy in laminar flow field and its application in heat transfer enhancement Int J Heat Mass Transfer 52 4669-4672
[6]  
Tao W Q(2016)Heat and fluid flow in high-power LED packaging and applications Prog Energy Combust Sci 56 1-32
[7]  
He Y L(2016)Analysis of micro-channel heat sinks with rectangular-shaped flow obstructions Numer Heat Transfer Part A-Appl 69 335-351
[8]  
Chen L(2020)Numerical study on flow and heat transfer characteristics of microchannel designed using topological optimizations method Sci China Technol Sci 63 105-115
[9]  
He Y L(1996)Street network theory of organization in nature J Adv Transport 30 85-107
[10]  
Tao W Q(2006)Constructal theory: From engineering to physics, and how flow systems develop shape and structure Appl Mech Rev 59 269-282